Section 4
Protection functions
Parameter
Values (Range)
Reference power
0.050...1.000
Characteristic angle
-179...180
Time multiplier
0.05...2.00
Operating curve type
5=ANSI DT
15=IEC DT
20=Wattmetric
IDMT
Trip delay time
60...200000
Table 402:
32N Non group settings (Basic)
Parameter
Values (Range)
Operation
1=enable
5=disable
Table 403:
32N Non group settings (Advanced)
Parameter
Values (Range)
Measurement mode
1=RMS
2=DFT
3=Peak-to-Peak
Correction angle
0.0...10.0
Min trip current
0.010...1.000
Min trip voltage
0.01...1.00
Reset delay time
0...60000
Pol reversal
0=False
1=True
Io signal Sel
1=Measured IG
2=Calculated I0
Vg or V0
1=Measured VG
2=Calculated V0
422
Unit
Step
Default
xPn
0.001
0.150
deg
1
-90
0.01
1.00
15=IEC DT
ms
10
60
Unit
Step
Default
1=enable
Unit
Step
Default
2=DFT
deg
0.1
2.0
xIn
0.001
0.010
xUn
0.01
0.01
ms
1
20
0=False
1=Measured IG
1=Measured VG
1MAC059074-MB A
Description
Reference value of residual power for
Wattmetric IDMT curves
Characteristic angle
Time multiplier for Wattmetric IDMT curves
Selection of time delay curve type
Trip delay time for definite time
Description
Operation Disable / Enable
Description
Selects used current measurement mode
Angle correction
Minimum trip current
Minimum trip voltage
Reset delay time
Rotate polarizing quantity
Selection for used Io signal
Selection for used polarization signal
Technical Manual