Settings - ABB 615 series Technical Manual

Hide thumbs Also See for 615 series:
Table of Contents

Advertisement

1MAC059074-MB A
5.7.7
Table 719:
21FL Group settings (Basic)
Parameter
Values (Range)
Z Max phase load
1.0...10000.0
Ph leakage Ris
20...1000000
Ph capacitive React
10...1000000
R1 line section A
0.000...1000.000
X1 line section A
0.000...1000.000
R0 line section A
0.000...1000.000
X0 line section A
0.000...1000.000
Line Len section A
0.000...1000.000
Table 720:
21FL Group settings (Advanced)
Parameter
Values (Range)
High alarm Dis limit
0.000...1.000
Low alarm Dis limit
0.000...1.000
Equivalent load Dis
0.00...1.00
R1 line section B
0.000...1000.000
X1 line section B
0.000...1000.000
R0 line section B
0.000...1000.000
X0 line section B
0.000...1000.000
Line Len section B
0.000...1000.000
R1 line section C
0.000...1000.000
X1 line section C
0.000...1000.000
R0 line section C
0.000...1000.000
X0 line section C
0.000...1000.000
Line Len section C
0.000...1000.000
615 series ANSI
Technical Manual

Settings

Unit
Step
ohm
0.1
ohm
1
ohm
1
ohm / pu
0.001
ohm / pu
0.001
ohm / pu
0.001
ohm / pu
0.001
pu
0.001
Unit
Step
pu
0.001
pu
0.001
0.01
ohm / pu
0.001
ohm / pu
0.001
ohm / pu
0.001
ohm / pu
0.001
pu
0.001
ohm / pu
0.001
ohm / pu
0.001
ohm / pu
0.001
ohm / pu
0.001
pu
0.001
Protection related functions
Default
Description
80.0
Impedance per phase of max. load, overcurr./
under-imp., PSL
210000
Line PhE leakage resistance in primary ohms
7000
Line PhE capacitive reactance in primary ohms
1.000
Positive sequence line resistance, line section
A
1.000
Positive sequence line reactance, line section
A
4.000
Zero sequence line resistance, line section A
4.000
Zero sequence line reactance, line section A
0.000
Line length, section A
Default
Description
0.000
High alarm limit for calculated distance
0.000
Low alarm limit for calculated distance
0.50
Equivalent load distance when EF algorithm
equals to load modelling
1.000
Positive sequence line resistance, line section
B
1.000
Positive sequence line reactance, line section
B
4.000
Zero sequence line resistance, line section B
4.000
Zero sequence line reactance, line section B
0.000
Line length, section B
1.000
Positive sequence line resistance, line section
C
1.000
Positive sequence line reactance, line section
C
4.000
Zero sequence line resistance, line section C
4.000
Zero sequence line reactance, line section C
0.000
Line length, section C
Section 5