Settings - ABB 615 series Technical Manual

Hide thumbs Also See for 615 series:
Table of Contents

Advertisement

1MAC059074-MB A
8.1.5.4
Table 803:
VA,VB,VC Non group settings (Basic)
Parameter
Values (Range)
Operation
1=enable
5=disable
Num of phases
1=1 out of 3
2=2 out of 3
3=3 out of 3
V high high limit
0.00...4.00
V high limit
0.00...4.00
V low limit
0.00...4.00
V low low limit
0.00...4.00
V deadband
100...100000
Table 804:
VA,VB,VC Non group settings (Advanced)
Parameter
Values (Range)
Measurement mode
1=RMS
2=DFT
8.1.5.5
615 series ANSI
Technical Manual
Table 802:
VA,VB,VC Output signals
Name
Type
HIGH_ALARM
BOOLEAN
HIGH_WARN
BOOLEAN
LOW_WARN
BOOLEAN
LOW_ALARM
BOOLEAN

Settings

Unit
Step
xUn
1
xUn
1
xUn
1
xUn
1
1
Unit
Step
Monitored data
Table 805:
VA,VB,VC Monitored data
Name
Type
VAB-kV
FLOAT32
VBC-kV
FLOAT32
VCA-kV
FLOAT32
Table continues on next page
Measurement functions
Description
High alarm
High warning
Low warning
Low alarm
Default
Description
1=enable
Operation Disable / Enable
1=1 out of 3
Number of phases required by limit supervision
1.40
High alarm voltage limit
1.20
High warning voltage limit
0.00
Low warning voltage limit
0.00
Low alarm voltage limit
10000
Deadband configuration value for integral
calculation. (percentage of difference between
min and max as 0,001 % s)
Default
Description
2=DFT
Selects used measurement mode
Values (Range)
Unit
0.00...4.00
xUn
0.00...4.00
xUn
0.00...4.00
xUn
Section 8
Description
Measured phase to phase
voltage amplitude phase AB
Measured phase to phase
voltage amplitude phase BC
Measured phase to phase
voltage amplitude phase CA
911