ABB 615 series Technical Manual page 417

Hide thumbs Also See for 615 series:
Table of Contents

Advertisement

1MAC059074-MB A
615 series ANSI
Technical Manual
IG
Directional
calculation
VG
RCA_CTL
Residual
power
calculation
Blocking
BLOCK
logic
GUID-ADCF64D0-2E7F-4806-BE05-9F9D59137D9D V1 EN
Figure 197:
Function module diagram
Directional calculation
The Directional calculation module monitors the angle between the operating quantity
(residual current IG or I0) and polarizing quantity (residual voltage VG or V0). The
operating quantity can be selected with the setting Io signal Sel. The selectable options are
"Measured IG" and "Calculated I0". The polarizing quantity can be selected with the
setting Pol signal Sel. The selectable options are "Measured VG" and "Calculated V0".
When the angle between operating quantity and polarizing quantity after considering the
Characteristic angle setting is in the operation sector, the module sends an enabling signal
to Level detector. The directional operation is selected with the Directional mode setting.
Either the "Forward" or "Reverse" operation mode can be selected. The direction of fault
is calculated based on the phase angle difference between the operating quantity IG or I0
and polarizing quantity VG or V0, and the value (ANGLE) is available in the monitored
data view.
In the phasor diagrams representing the operation of 32N, the polarity of the polarizing
quantity (residual voltage VG or V0) is reversed. Reversing is done by switching the
polarity of the residual current measuring channel (See the connection diagram in the
application manual).
If the angle difference lies between -90° to 0° or 0° to +90°, a forward-direction fault is
considered. If the phase angle difference lies within -90° to -180° or +90° to +180°, a
reverse-direction fault is detected. Thus, the normal width of a sector is 180°.
Timer
Level
detector
t
t
Section 4
Protection functions
TRIP
PICKUP
411

Advertisement

Table of Contents
loading

Table of Contents