ABB 615 series Technical Manual page 69

Hide thumbs Also See for 615 series:
Table of Contents

Advertisement

1MAC059074-MB A
Table 15:
Ethernet rear port settings
Parameter
Values (Range)
IP address
Subnet mask
Default gateway
Mac address
Table 16:
General system settings
Parameter
Values (Range)
Rated frequency
1=50Hz
2=60Hz
Phase rotation
1=ABC
2=ACB
Blocking mode
1=Freeze timer
2=Block all
3=Block TRIP
output
1)
Bay name
IDMT Sat point
10...50
0=Disable
3)
Frequency adaptivity
1=Enable
SMV Max Delay
0=1.90 1.58 ms
1=3.15 2.62 ms
2=4.40 3.67 ms
3=5.65 4.71 ms
4=6.90 5.75 ms
1) Used in the protection relay main menu header and as part of the disturbance recording identification
2) Depending on the product variant
3) Available only in REG615
Table 17:
HMI settings
Parameter
Values (Range)
FB naming convention
1=IEC61850
2=IEC60617
3=IEC-ANSI
Default view
1=Measurements
2=Main menu
3=SLD page 1
Backlight timeout
1...60
Web HMI mode
1=Active read only
2=Active
3=Disabled
Table continues on next page
615 series ANSI
Technical Manual
Unit
Step
Default
192.168.2.10
255.255.255.0
192.168.2.1
XX-XX-XX-XX-
XX-XX
Unit
Step
Default
1=50Hz
1=ABC
1=Freeze timer
REF615
I/I>
1
50
0=Disable
1=3.15 2.62 ms
Unit
Step
Default
1=IEC61850
1=Measurements
min
1
3
3=Disabled
Description
IP address for rear port(s)
Subnet mask for rear port(s)
Default gateway for rear port(s)
Mac address for rear port(s)
Description
Rated frequency of the network
Phase rotation order
Behavior for function BLOCK inputs
Bay name in system
2)
Overcurrent IDMT saturation point
Enabling frequency adaptivity
SMV Maximum allowed delay
Description
FB naming convention used in IED
LHMI default view
LHMI backlight timeout
Web HMI functionality
Section 3
Basic functions
63

Advertisement

Table of Contents
loading

Table of Contents