Settings - ABB 615 series Technical Manual

Hide thumbs Also See for 615 series:
Table of Contents

Advertisement

1MAC059074-MB A
6.3.8
Table 753:
MCS-A Non group settings (Basic)
Parameter
Values (Range)
Operation
1=enable
5=disable
Pickup value
1.0...100.0
Alarm delay time
100...300000
Alarm output mode
1=Non-latched
3=Lockout
Table 754:
MCS-A Non group settings (Advanced)
Parameter
Values (Range)
Reset delay time
0...60000
Measurement mode
2=DFT
3=Peak-to-Peak
Table 755:
MCS-B Non group settings (Basic)
Parameter
Values (Range)
Operation
1=enable
5=disable
Pickup value
1.0...100.0
Alarm delay time
100...300000
Alarm output mode
1=Non-latched
3=Lockout
Table 756:
MCS-B Non group settings (Advanced)
Parameter
Values (Range)
Reset delay time
0...60000
Measurement mode
2=DFT
3=Peak-to-Peak
615 series ANSI
Technical Manual

Settings

Unit
Step
%In
0.1
ms
10
Unit
Step
ms
10
Unit
Step
%In
0.1
ms
10
Unit
Step
ms
10
Default
Description
1=enable
Operation Disable / Enable
10.0
Pickup value, percentage of the nominal
current
3000
Alarm delay time
3=Lockout
Select the operation mode for alarm output
Default
Description
20
Reset delay time
2=DFT
Selects used measurement mode
Default
Description
1=enable
Operation Disable / Enable
10.0
Pickup value, percentage of the nominal
current
3000
Alarm delay time
3=Lockout
Select the operation mode for alarm output
Default
Description
20
Reset delay time
2=DFT
Selects used measurement mode
Section 6
Supervision functions
859