Settings - ABB 615 series Technical Manual

Hide thumbs Also See for 615 series:
Table of Contents

Advertisement

1MAC059074-MB A
4.5.7.7
Table 568:
27RT Group settings (Basic)
Parameter
Values (Range)
Voltage pickup value
0.05...1.20
Table 569:
27RT Non group settings (Basic)
Parameter
Values (Range)
Operation
1=enable
5=disable
Num of pickup phases
4=Exactly 1 of 3
5=Exactly 2 of 3
6=Exactly 3 of 3
Voltage selection
1=Highest Ph-to-E
2=Lowest Ph-to-E
3=Highest Ph-to-
Ph
4=Lowest Ph-to-Ph
5=Positive Seq
Active coordinates
1...10
Voltage level 1
0.00...1.20
Voltage level 2
0.00...1.20
Voltage level 3
0.00...1.20
Voltage level 4
0.00...1.20
Voltage level 5
0.00...1.20
Voltage level 6
0.00...1.20
Voltage level 7
0.00...1.20
Voltage level 8
0.00...1.20
Voltage level 9
0.00...1.20
Voltage level 10
0.00...1.20
Recovery time 1
0...300000
Recovery time 2
0...300000
Recovery time 3
0...300000
Recovery time 4
0...300000
Recovery time 5
0...300000
Recovery time 6
0...300000
Recovery time 7
0...300000
Recovery time 8
0...300000
Recovery time 9
0...300000
Recovery time 10
0...300000
615 series ANSI
Technical Manual

Settings

Unit
Step
xUn
0.01
Unit
Step
1
xUn
0.01
xUn
0.01
xUn
0.01
xUn
0.01
xUn
0.01
xUn
0.01
xUn
0.01
xUn
0.01
xUn
0.01
xUn
0.01
ms
1
ms
1
ms
1
ms
1
ms
1
ms
1
ms
1
ms
1
ms
1
ms
1
Default
Description
0.90
Voltage value below which function pickups
Default
Description
1=enable
Operation Disable / Enable
4=Exactly 1 of 3
Number of faulty phases
4=Lowest Ph-to-
Parameter to select voltage for curve
Ph
monitoring
3
Coordinates used for defining LVRT curve
0.20
1st voltage coordinate for defining LVRT curve
0.80
2nd voltage coordinate for defining LVRT curve
0.90
3rd voltage coordinate for defining LVRT curve
0.90
4th voltage coordinate for defining LVRT curve
0.90
5th voltage coordinate for defining LVRT curve
0.90
6th voltage coordinate for defining LVRT curve
0.90
7th voltage coordinate for defining LVRT curve
0.90
8th voltage coordinate for defining LVRT curve
0.90
9th voltage coordinate for defining LVRT curve
0.90
10th voltage coordinate for defining LVRT
curve
500
1st time coordinate for defining LVRT curve
1000
2nd time coordinate for defining LVRT curve
10000
3rd time coordinate for defining LVRT curve
10000
4th time coordinate for defining LVRT curve
10000
5th time coordinate for defining LVRT curve
10000
6th time coordinate for defining LVRT curve
10000
7th time coordinate for defining LVRT curve
10000
8th time coordinate for defining LVRT curve
10000
9th time coordinate for defining LVRT curve
10000
10th time coordinate for defining LVRT curve
Section 4
Protection functions
665

Advertisement

Table of Contents
loading

Table of Contents