Basic functions
Table 7:
Analog input settings, phase voltages
Parameter
Values (Range)
Primary voltage
0.100...440.000
Secondary voltage
60...210
VT connection
1=Wye
2=Delta
3=VAB
4=VA
Amplitude corr. A
0.9000...1.1000
Amplitude corr. B
0.9000...1.1000
Amplitude corr. C
0.9000...1.1000
Division ratio
1000...20000
Voltage input type
1=Voltage trafo
3=CVD sensor
Angle Corr A
-20.0000...20.0000
Angle Corr B
-20.0000...20.0000
Angle Corr C
-20.0000...20.0000
Table 8:
Analog input settings, residual voltage
Parameter
Values (Range)
Primary voltage
0.100...440.000
Secondary voltage
60...210
Amplitude corr.
0.9000...1.1000
Angle correction
-20.0000...20.0000
1) In 9-2 applications, Primary voltage maximum is limited to 126 kV.
60
Unit
Step
Default
kV
0.001
V
1
0.0001
0.0001
0.0001
1
deg
0.0001
deg
0.0001
deg
0.0001
Unit
Step
Default
kV
0.001
1)
V
1
0.0001
deg
0.0001
Description
20.000
Primary rated voltage
100
Secondary rated voltage
2=Delta
Voltage transducer measurement connection
1.0000
Phase A Voltage phasor magnitude correction
of an external voltage transformer
1.0000
Phase B Voltage phasor magnitude correction
of an external voltage transformer
1.0000
Phase C Voltage phasor magnitude correction
of an external voltage transformer
10000
Voltage sensor division ratio
1=Voltage trafo
Type of the voltage input
0.0000
Phase A Voltage phasor angle correction of an
external voltage transformer
0.0000
Phase B Voltage phasor angle correction of an
external voltage transformer
0.0000
Phase C Voltage phasor angle correction of an
external voltage transformer
Description
11.547
Primary voltage
100
Secondary voltage
1.0000
Amplitude correction
0.0000
Angle correction factor
1MAC059074-MB A