Section 4
Protection functions
376
E
A
E
B
E
C
R
n
VG
Uo               
L
cc
R
cc
Reverse fault:
Yo ≈ ‐j*I
eFd
GUID-2C307D73-EF4A-479A-A6E5-47CAC730188C V1 EN
Figure 176:
Admittance calculation during a reverse fault
R
Resistance of the parallel resistor
CC
L
Inductance of the compensation coil
CC
R
Resistance of the neutral grounding resistor
n
Y
Phase-to-ground admittance of the protected feeder
Fd
Y
Phase-to-ground admittance of the background network
Bg
For example, in a 15 kV compensated network with the magnitude of the ground-fault
current in the protected feeder being 10 A (Rf = 0 Ω), the theoretical value for the
measured admittance during a ground fault in the reverse direction, that is, outside the
protected feeder, can be calculated.
IG
Io               
A    B    C
Protected feeder             
~
~
~
Background network
Im(Yo)
Re(Yo)
/U
Vph
ph
1MAC059074-MB A
Y
Fd
Reverse 
Fault
Y
Bg
(I
‐ I
)              
I
eTot
eFd
eFd
615 series ANSI
Technical Manual