Settings - ABB 615 series Technical Manual

Hide thumbs Also See for 615 series:
Table of Contents

Advertisement

1MAC059074-MB A
4.1.2.9
Table 246:
67/51P Group settings (Basic)
Parameter
Values (Range)
Pickup value
0.05...5.00
Pickup value mult
0.8...10.0
Time multiplier
0.05...15.00
Trip delay time
40...200000
Table continues on next page
615 series ANSI
Technical Manual
Table 243:
67/50P Input signals
Name
Type
I_A
SIGNAL
I_B
SIGNAL
I_C
SIGNAL
I
SIGNAL
2
V_A_AB
SIGNAL
V_B_BC
SIGNAL
V_C_CA
SIGNAL
V
SIGNAL
1
V
SIGNAL
2
BLOCK
BOOLEAN
ENA_MULT
BOOLEAN
NON_DIR
BOOLEAN
Table 244:
67/51P Output signals
Name
Type
TRIP
BOOLEAN
PICKUP
BOOLEAN
Table 245:
67/50P Output signals
Name
Type
PICKUP
BOOLEAN
TRIP
BOOLEAN

Settings

Unit
Step
xIn
0.01
0.1
0.01
ms
10
Default
Description
0
Phase A current
0
Phase B current
0
Phase C current
0
Negative phase sequence current
0
Phase to ground voltage A or phase to phase voltage AB
0
Phase to ground voltage B or phase to phase voltage BC
0
Phase to ground voltage C or phase to phase voltage
CA
0
Positive phase sequence voltage
0
Negative phase sequence voltage
0=False
Block signal for activating the blocking mode
0=False
Enable signal for current multiplier
0=False
Forces protection to non-directional
Description
Trip
Pickup
Description
Pickup
Trip
Default
Description
0.05
Pickup value
1.0
Multiplier for scaling the pickup value
1.00
Time multiplier in IEC/ANSI IDMT curves
40
Trip delay time
Section 4
Protection functions
251