Hide thumbs Also See for 615 series:
Table of Contents

Advertisement

Section 4
Protection functions
4.5.9.6
4.5.9.7
Table 582:
27R Non group settings (Basic)
Parameter
Values (Range)
Operation
1=enable
5=disable
Pickup value
0.05...1.20
Trip delay time
100...300000
Voltage selection
1=phase-to-earth
2=phase-to-phase
Num of phases
1=1 out of 3
2=2 out of 3
3=3 out of 3
Phase supervision
1=A or AB
2=B or BC
4=C or CA
7=A&B&C or
AB&BC&CA
Table 583:
27R Non group settings (Advanced)
Parameter
Values (Range)
Reset delay time
0...60000
676

Signals

Table 580:
27R Input signals
Name
Type
V_A_AB
SIGNAL
V_B_BC
SIGNAL
V_C_CA
SIGNAL
BLOCK
BOOLEAN
Table 581:
27R Output signals
Name
Type
U_LOW
BOOLEAN
Settings
Unit
Step
xUn
0.01
ms
100
Unit
Step
ms
1
Default
Description
0
Phase to ground voltage A or phase to phase voltage AB
0
Phase to ground voltage B or phase to phase voltage BC
0
Phase to ground voltage C or phase to phase voltage
CA
0=False
Block signal for activating the blocking mode
Description
Low remanent voltage
Default
Description
1=enable
Operation Disable / Enable
0.25
Pickup value
100
Trip delay time
2=phase-to-phase
Parameter to select phase or phase-to-phase
voltages
3=3 out of 3
Number of phases required for voltage
supervision
7=A&B&C or
Monitored voltage phase
AB&BC&CA
Default
Description
20
Reset delay time
1MAC059074-MB A
615 series ANSI
Technical Manual

Advertisement

Table of Contents
loading

Table of Contents