Basic functions
3.17.12.5
3.17.12.6
Table 194:
CTR Non group settings (Basic)
Parameter
Values (Range)
Operation
1=enable
5=disable
Counter load value
0...2147483647
Reset counter
0=Cancel
1=Reset
Load counter
0=Cancel
1=Load
3.17.12.7
3.18
198

Signals

Table 192:
CTR Input signals
Name
Type
UP_CNT
BOOLEAN
DOWN_CNT
BOOLEAN
RESET
BOOLEAN
LOAD
BOOLEAN
Table 193:
CTR Output signals
Name
Type
UPCNT_STS
BOOLEAN
DNCNT_STS
BOOLEAN

Settings

Unit
Step
1

Monitored data

Table 195:
CTR Monitored data
Name
Type
CNT_VAL
INT64

Factory settings restoration

In case of configuration data loss or any other file system error that prevents the protection
relay from working properly, the whole file system can be restored to the original factory
Default
Description
0=False
Input for up counting
0=False
Input for down counting
0=False
Reset input for counter
0=False
Load input for counter
Description
Status of the up counting
Status of the down counting
Default
Description
1=enable
Operation Disable / Enable
10000
Preset counter value
0=Cancel
Resets counter value
0=Cancel
Loads the counter to preset value
Values (Range)
Unit
0...2147483647
1MAC059074-MB A
Description
Output counter value
615 series ANSI
Technical Manual

Advertisement

Table of Contents
loading

Table of Contents