1MAC059074-MB A
4.7.3.6
4.7.3.7
Table 616:
21G Group settings (Basic)
Parameter
Values (Range)
Percentage reach
1...6000
Trip delay time
40...200000
615 series ANSI
Technical Manual
Function blocking guidelines
The operation of the underimpedance protection must be restrained if the voltage in one
or more phases suddenly drops close to zero without any significant change in the current
observed at the same time. This situation is considered as a fuse failure or a miniature
circuit breaker operation in the voltage transformer secondary circuit. The voltage drop
could cause an unwanted operation of the function block since the calculated impedance
could fall below the set operating limit even if there is no actual fault in the primary
system.
The blocking operation is provided by an external function block, the fuse failure
supervision 60, whose output is connected to the BLOCK input of 21G.

Signals

Table 614:
21G Input signals
Name
Type
I_A
SIGNAL
I_B
SIGNAL
I_C
SIGNAL
I
SIGNAL
1
V_A_AB
SIGNAL
V_B_BC
SIGNAL
V_C_CA
SIGNAL
V
SIGNAL
1
BLOCK
BOOLEAN
Table 615:
21G Output signals
Name
Type
TRIP
BOOLEAN
PICKUP
BOOLEAN
Settings
Unit
Step
%Zn
1
ms
10
Default
Description
0
Phase A current
0
Phase B current
0
Phase C current
0
Positive sequence current
0
Phase-to-ground voltage A or phase-to-phase voltage
AB
0
Phase-to-ground voltage B or phase-to-phase voltage
BC
0
Phase-to-ground voltage C or phase-to-phase voltage
CA
0
Positive phase sequence voltage
0=False
Block signal for activating the blocking mode
Description
Trip
Pickup
Default
Description
7
Radius of the origin centric circle
200
Trip delay time
Section 4
Protection functions
715