Section 3
Basic functions
88
For example, six setting groups can be controlled with three binary inputs. The SG
operation mode is set to "Logic mode 2" and inputs BI_SG_2 and BI_SG_5 are
connected together the same way as inputs BI_SG_3 and BI_SG_6.
Table 35:
SG operation mode = "Logic mode 1"
BI_SG_2
BI_SG_3
FALSE
FALSE
TRUE
FALSE
any
TRUE
any
any
any
any
any
any
Table 36:
SG operation mode = "Logic mode 2"
BI_SG_2
BI_SG_3
FALSE
FALSE
TRUE
FALSE
any
TRUE
any
any
any
any
any
any
The setting group 1 can be copied to any other or all groups from HMI (Copy group 1).
Input
BI_SG_4
BI_SG_5
FALSE
FALSE
FALSE
FALSE
FALSE
FALSE
TRUE
FALSE
any
TRUE
any
any
Input
BI_SG_4
BI_SG_5
FALSE
any
FALSE
any
FALSE
any
TRUE
FALSE
TRUE
TRUE
TRUE
any
1MAC059074-MB A
BI_SG_6
Active group
FALSE
1
FALSE
2
FALSE
3
FALSE
4
FALSE
5
TRUE
6
BI_SG_6
Active group
any
1
any
2
any
3
FALSE
4
FALSE
5
TRUE
6
615 series ANSI
Technical Manual