Settings - ABB 615 series Technical Manual

Hide thumbs Also See for 615 series:
Table of Contents

Advertisement

Section 5
Protection related functions
5.3.7
Table 687:
86/94 Non group settings (Basic)
Parameter
Values (Range)
Operation
1=enable
5=disable
Trip pulse time
20...60000
Trip output mode
1=Non-latched
2=Latched
3=Lockout
5.3.8
5.3.9
5.4
5.4.1
788

Settings

Unit
Step
ms
1
Monitored data
Table 688:
86/94 Monitored data
Name
Type
86/94
Enum
Technical revision history
Table 689:
86/94 Technical revision history
Technical revision
B
C
D
E
F
High-impedance fault detection HIZ
Identification
Function description
High-impedance fault detection
Default
Description
1=enable
Operation Disable / Enable
250
Minimum duration of trip output signal
1=Non-latched
Select the operation mode for trip output
Values (Range)
Unit
1=Enabled
2=blocked
3=test
4=test/blocked
5=Disabled
Change
-
-
Internal improvement.
Trip output mode default setting is changed
Setting
to "Latched".
Internal improvement.
IEC 61850
IEC 60617
identification
identification
PHIZ
HIF
1MAC059074-MB A
Description
Status
ANSI/IEEE C37.2
device number
HIZ
615 series ANSI
Technical Manual