Signals; Settings - ABB 615 series Technical Manual

Hide thumbs Also See for 615 series:
Table of Contents

Advertisement

Section 4
Protection functions
4.3.3.6
4.3.3.7
Table 444:
87LOZREF Group settings (Basic)
Parameter
Values (Range)
Trip value
5.0...50.0
Table 445:
87LOZREF Group settings (Advanced)
Parameter
Values (Range)
Minimum trip time
40...300000
Restraint mode
1=None
2=Harmonic2
Pickup value 2.H
10...50
548
the neutral current IG_2H / IG. Typically, the second harmonic content of the neutral
current at the magnetizing inrush is higher than that of the phase currents.

Signals

Table 442:
87LOZREF Input signals
Name
Type
I_A
SIGNAL
I_B
SIGNAL
I_C
SIGNAL
IG
SIGNAL
BLOCK
BOOLEAN
Table 443:
87LOZREF Output signals
Name
Type
TRIP
BOOLEAN
PICKUP
BOOLEAN
BLK2H
BOOLEAN

Settings

Unit
Step
%In
1.0
Unit
Step
ms
1
%
1
Default
Description
0
Phase A current
0
Phase B current
0
Phase C current
0
Zero-sequence current
0=False
Block signal for activating the blocking mode
Description
Trip
Pickup
2nd harmonic block
Default
Description
5.0
Trip value
Default
Description
40
Minimum trip time
1=None
Restraint mode
50
The ratio of the 2. harmonic to fundamental
component required for blocking
1MAC059074-MB A
615 series ANSI
Technical Manual

Advertisement

Table of Contents
loading