Settings - ABB 615 series Technical Manual

Hide thumbs Also See for 615 series:
Table of Contents

Advertisement

Section 4
Protection functions
4.4.4.8
Table 504:
46M Group settings (Basic)
Parameter
Values (Range)
Pickup value
0.01...0.50
Operating curve type
5=ANSI DT
15=IEC DT
17=Inv. Curve A
18=Inv. Curve B
Machine time Mult
5.0...100.0
Trip delay time
100...120000
Table 505:
46M Non group settings (Basic)
Parameter
Values (Range)
Operation
1=enable
5=disable
Maximum trip time
500000...7200000
Minimum trip time
100...120000
Cooling time
5...7200
Table 506:
46M Non group settings (Advanced)
Parameter
Values (Range)
Rated current
0.30...2.00
Reset delay time
0...60000
608
Table 503:
46M Output signals
Name
Type
TRIP
BOOLEAN
PICKUP
BOOLEAN
BLK_RESTART
BOOLEAN

Settings

Unit
Step
xIn
0.01
0.1
ms
10
Unit
Step
ms
1000
ms
1
s
1
Unit
Step
xIn
0.01
ms
1
Description
Trip
Pickup
Overheated machine reconnection blocking
Default
Description
0.20
Pickup value
15=IEC DT
Selection of time delay curve type
5.0
Machine related time constant
1000
Trip delay time
Default
Description
1=enable
Operation Disable / Enable
1000000
Max trip time regardless of the inverse
characteristic
100
Minimum trip time for IDMT curves
50
Time required to cool the machine
Default
Description
1.00
Rated current (Ir) of the machine (used only in
the IDMT)
20
Reset delay time
1MAC059074-MB A
615 series ANSI
Technical Manual