Settings - ABB 615 series Technical Manual

Hide thumbs Also See for 615 series:
Table of Contents

Advertisement

1MAC059074-MB A
4.5.3.7
Table 534:
59N,59G Group settings (Basic)
Parameter
Values (Range)
Pickup value
0.010...1.000
Trip delay time
40...300000
Table 535:
59N,59G Non group settings (Basic)
Parameter
Values (Range)
Operation
1=enable
5=disable
VG/V0 Select
1=Measured VG
2=Calculated V0
Table 536:
59N,59G Non group settings (Advanced)
Parameter
Values (Range)
Reset delay time
0...60000
4.5.3.8
4.5.3.9
615 series ANSI
Technical Manual

Settings

Unit
Step
xUn
0.001
ms
1
Unit
Step
Unit
Step
ms
1
Monitored data
Table 537:
59N,59G Monitored data
Name
Type
PICKUP_DUR
FLOAT32
59N,59G
Enum
Technical data
Table 538:
59N, 59G Technical data
Characteristic
Operation accuracy
1)2)
Pickup time
V
value
Table continues on next page
Default
0.030
40
Default
1=enable
1=Measured VG
Default
20
Values (Range)
0.00...100.00
1=Enabled
2=blocked
3=test
4=test/blocked
5=Disabled
Value
Depending on the frequency of the measured
voltage: f
±1.5% of the set value or ±0.002 × V
Minimum
Pickup
= 2 × set
48 ms
Fault
Protection functions
Description
Pickup value
Trip delay time
Description
Operation Disable / Enable
Selection for used VG/V0 signal
Description
Reset delay time
Unit
Description
%
Ratio of pickup time / trip time
Status
±2 Hz
n
Typical
51 ms
Section 4
n
Maximum
54 ms
631