ABB 615 series Technical Manual page 551

Hide thumbs Also See for 615 series:
Table of Contents

Advertisement

1MAC059074-MB A
615 series ANSI
Technical Manual
P2
A
S2
S1
B
C
1/5A
1/5A
1/5A
N
N
N
I_A
I_B
I_C
GUID-F72BF76A-0864-4A98-A352-D597C5864AD8 V1 EN
Figure 272:
Connection of the current transformers of Type 2. The phase currents
and the neutral current have equal directions at an external ground-fault
situation. Phase grounding is inside and neutral grounding is outside the
area to be protected.
P1
P2
A
S1 S2
B
C
1/5A
1/5A
1/5A
N
N
N
I_C
I_B
I_A
GUID-D870C784-0241-4DC6-B937-B27850200227 V1 EN
Figure 273:
Connection of the current transformers of Type 2. The phase currents
and the neutral current have equal directions at an external ground-fault
situation. Phase grounding is outside and neutral grounding is inside the
area to be protected.
P1
Section 4
Protection functions
P2
P1
S2
S1
1/5A
N
IG
P1
P2
S1 S2
1/5A
N
IG
545