Section 3
Basic functions
Table 181:
Station authority level "L,S,R" using R/L button
L/R Control
R/L button
CTRL.LLN0.LocSta
Local
FALSE
Remote
FALSE
Remote
TRUE
Off
FALSE
1) Station client reserves the control operating by writing controllable point LocSta.
2) Client IEC 61850 command originator category is remote.
3) Client IEC 61850 command originator category is station.
186
LOCAL
REMOTE
IEC 61850
remote
IEC 61850
IEC 61850
station
station
IED
GUID-7BC51FAF-B097-4CD9-AFF4-6D1F3D548C7F V1 EN
Figure 95:
Station authority is "L,S,R"
When the station authority level "L,S,R" is used, the control access can be selected using
R/L button or CONTROL function block. IEC 61850 data object CTRL.LLN0.LocSta
and CONTROL function block input CTRL_STA are applicable for this station authority
level.
Station control access can be reserved by using R/L button or CONTROL function block
together with IEC 61850 data object CTRL.LLN0.LocSta.
L/R Control status
CTRL.LLN0.MltLev
1)
FALSE
FALSE
FALSE
FALSE
STATION
IEC 61850
IEC 61850
remote
remote
IEC 61850
station
IED
IED
L/R state
CTRL.LLN0.LocKeyHMI
1
2
3
0
1MAC059074-MB A
OFF
IEC 61850
remote
IEC 61850
station
IED
Control access
Local user
IEC 61850
client
2)
x
x
615 series ANSI
Technical Manual
IEC 61850
client
3)
x