1MAC059074-MB A
5.8.5
5.8.6
5.8.7
Table 728:
SOTF Group settings (Basic)
Parameter
Values (Range)
Trip delay time
0...60000
615 series ANSI
Technical Manual
SOTF control
The SOTF control is activated when CB_CL_CMD circuit breaker closing command input
is activated. The module is kept active until the set SOTF reset time is exceeded after the
CB_CL_CMD is deactivated. The TRIP output is activated when a fault indication signal
is received from the Trigger module while the SOTF control is still active.

Application

The CB_CL_CMD input activates SOTF. In the standard configuration, the breaker close
command should be connected to this input. The SOTF reset time setting parameter is used
for keeping SOTF active for a certain time after the CB close command is executed.
The overcurrent high and instantaneous signals, for example, the 50P-3 PICKUP signal is
connected to the function PICKUP input. When the SOTF control module is active and the
PICKUP input is activated, the function trips instantaneously without any delays.
The overcurrent low stage signals, for example, 51P PICKUP signal is connected to the
function PICKUP_DLYD input. The setting parameter Trip delay time is used to delay the
operation in case of inrush situation.
Signals
Table 726:
SOTF Input signals
Name
Type
PICKUP
BOOLEAN
PICKUP_DLYD
BOOLEAN
CB_CL_CMD
BOOLEAN
BLOCK
BOOLEAN
Table 727:
SOTF Output signals
Name
Type
TRIP
BOOLEAN
Settings
Unit
Step
ms
1
Protection related functions
Default
Description
0=False
Pickup from function to be accelerated by SOTF
0=False
Pickup from function to be accelerated with delay by
SOTF
0=False
External enabling of SOTF by CB close command
0=False
Block of function
Description
Trip
Default
Description
0
Time delay for pickup input
Section 5
833