Application

In the field of distribution and sub-transmission automation, the reliable control and status
indication of primary switching components both locally and remotely is in a significant
role. These features are needed especially in modern remote controlled substations. The
application area of 52-TOC, 29DS and 29GS functions covers remote and local status
indication of, for example, disconnectors, air-break switches and grounding switches,
which represent the lowest level of power switching devices without short-circuit
breaking capability.
Signals
Table 882:
52-TOC,29DS Input signals
Name
Type
POSOPEN
BOOLEAN
POSCLOSE
BOOLEAN
1) Not available for monitoring
Table 883:
29GS Input signals
Name
Type
POSOPEN
BOOLEAN
POSCLOSE
BOOLEAN
1) Not available for monitoring
Status
Output
POSITION
OKPOS
(Monitored data)
1=Open
1=True
2=Closed
1=True
3=Faulty/Bad
0=False
(11)
0=Intermediat
0=False
e (00)
Default
Description
0=False
Signal for open position of apparatus from I/O
0=False
Signal for close position of apparatus from I/O
Default
Description
0=False
Signal for open position of apparatus from I/O
0=False
Signal for close position of apparatus from I/O
Section 9
Control functions
OPENPOS
CLOSEPOS
1=True
0=False
0=False
1=True
0=False
0=False
0=False
0=False
1)
1)
1)
1)