Section 3
Basic functions
3.14.1.2
3.14.1.3
Table 61:
SMVSENDER Settings
Parameter
Values (Range)
Operation
1=on
5=off
3.14.2
3.14.2.1
3.14.2.2
3.14.2.3
130
Functionality
The SMVSENDER function block is used for activating the SMV sending functionality.
It adds/removes the sampled value control block and the related data set into/from the
sending device's configuration. It has no input or output signals.
SMVSENDER can be disabled with the Operation setting value "off". If the
SMVSENDER is disabled from the LHMI, it can only be enabled from the LHMI. When
disabled, the sending of the samples values is disabled.
Settings
Unit
IEC 61850-9-2 LE sampled values receiving SMVRECEIVER
Function block
SMVRECEIVER
UL1
UL2
UL3
Uo
GUID-EB0B6F8A-724A-4090-A94B-0BD935BB03F4 V1 EN
Figure 43:
Function block
Functionality
The SMVRECEIVER function block is used for activating the SMV receiving
functionality.
Signals
Table 62:
SMVRECEIVER Output signals
Name
UL1
UL2
UL3
U0
Step
Default
1=on
Type
INT32-UL1
INT32-UL2
INT32-UL3
INT32-Uo
1MAC059074-MB A
Description
Operation
Description
IEC61850-9-2 phase 1 voltage
IEC61850-9-2 phase 2 voltage
IEC61850-9-2 phase 3 voltage
IEC61850-9-2 residual voltage
615 series ANSI
Technical Manual