Technical Data - ABB 615 series Technical Manual

Hide thumbs Also See for 615 series:
Table of Contents

Advertisement

1MAC059074-MB A
4.8.2.9
4.8.3
4.8.3.1
615 series ANSI
Technical Manual
Name
Type
S
FLOAT32
PF_ANGLE
FLOAT32
32R/32O
Enum

Technical data

Table 636:
32R/32O Technical data
Characteristic
1)
Operation accuracy
2)3)
Pickup time
Reset time
Reset ratio
Trip time accuracy
Suppression of harmonics
Measurement mode = "Pos Seq" (default)
1)
2) V = V
, f
= 50 Hz, results based on statistical distribution of 1000 measurements
n
n
3) Includes the delay of the signal output contact
Directional reactive power undervoltage protection 32Q-27
Identification
Description
Directional reactive power undervoltage
protection
Values (Range)
Unit
0.000...160.000
xSn
-180.00...180.00
deg
1=Enabled
2=blocked
3=test
4=test/blocked
5=Disabled
Value
Depending on the frequency of the measured current
and voltage:
f = f
±2 Hz
n
Power measurement accuracy ±3% of the set value
or ±0.002 × S
n
Phase angle: ±2°
Typically 45 ms
Typically 30 ms
Typically 0.94
±1.0% of the set value of ±20 ms
-50 dB at f = n × f
IEC 61850
IEC 60617
identification
identification
DQPTUV
Q> ->,3U<
Section 4
Protection functions
Description
Apparent power
Power factor angle
Status
, where n = 2, 3, 4, 5,...
n
ANSI/IEEE C37.2
device number
32Q-27
733

Advertisement

Table of Contents
loading

Table of Contents