Settings - ABB 615 series Technical Manual

Hide thumbs Also See for 615 series:
Table of Contents

Advertisement

Section 4
Protection functions
4.3.2.8
Table 435:
87T Group settings (Basic)
Parameter
Values (Range)
High trip value
500...3000
Low trip value
5...50
Slope section 2
10...50
End section 2
100...500
Restraint Mode
5=Waveform
6=2.h + waveform
8=5.h + waveform
9=2.h + 5.h + wav
Pickup value 2.H
7...20
Pickup value 5.H
10...50
532
Name
Type
I_C(2)
SIGNAL
BLOCK
BOOLEAN
BLK_OPR_LS
BOOLEAN
BLK_OPR_HS
BOOLEAN
Table 434:
87T Output signals
Name
Type
TRIP
BOOLEAN
OPR_LS
BOOLEAN
OPR_HS
BOOLEAN
BLKD2H
BOOLEAN
BLKD5H
BOOLEAN
BLKDWAV
BOOLEAN

Settings

Unit
Step
%Ir
10
%Ir
1
%
1
%Ir
1
%
1
%
1
Default
Description
0
Phase C secondary current
0=False
Block
0=False
Blocks trip outputs from biased stage
0=False
Blocks trip outputs from instantaneous stage
Description
Trip combined
Trip from low set
Trip from high set
2nd harmonic restraint block status
5th harmonic restraint block status
Waveform blocking status
Default
Description
1000
Instantaneous stage setting
20
Basic setting for biased operation
30
Slope of the second line of the operating
characteristics
150
Turn-point between the second and the third
line of the operating characteristics
9=2.h + 5.h + wav
Restraint Mode
15
The ratio of the 2. harmonic to fundamental
component required for blocking
35
The ratio of the 5. harmonic to fundamental
component required for blocking
1MAC059074-MB A
615 series ANSI
Technical Manual

Advertisement

Table of Contents
loading