ABB 615 series Technical Manual page 329

Hide thumbs Also See for 615 series:
Table of Contents

Advertisement

1MAC059074-MB A
Parameter
Values (Range)
Curve parameter C
0.02...2.00
Curve parameter D
0.46...30.00
Curve parameter E
0.0...1.0
Table 334:
50N,50G Non group settings (Advanced)
Parameter
Values (Range)
Minimum trip time
20...60000
Reset delay time
0...60000
Measurement mode
1=RMS
2=DFT
3=Peak-to-Peak
IG/I0 signal Sel
1=Measured IG
2=Calculated I0
Table 335:
50N-3,50G-3 Group settings (Basic)
Parameter
Values (Range)
Pickup value
1.00...40.00
Pickup value mult
0.8...10.0
Trip delay time
20...200000
Table 336:
50N-3,50G-3 Non group settings (Basic)
Parameter
Values (Range)
Operation
1=enable
5=disable
Table 337:
50N-3,50G-3 Non group settings (Advanced)
Parameter
Values (Range)
Reset delay time
0...60000
IG/I0 signal Sel
1=Measured IG
2=Calculated I0
615 series ANSI
Technical Manual
Unit
Step
Default
1
2.00
1
29.10
1
1.0
Unit
Step
Default
ms
1
20
ms
1
20
2=DFT
1=Measured IG
Unit
Step
Default
xIn
0.01
1.00
0.1
1.0
ms
10
20
Unit
Step
Default
1=enable
Unit
Step
Default
ms
1
20
1=Measured IG
Protection functions
Description
Parameter C for customer programmable
curve
Parameter D for customer programmable
curve
Parameter E for customer programmable
curve
Description
Minimum trip time for IDMT curves
Reset delay time
Selects used measurement mode
Measured IG or calculated I0
Description
Pickup value
Multiplier for scaling the pickup value
Trip delay time
Description
Operation Disable / Enable
Description
Reset delay time
Measured IG or calculated I0
Section 4
323