Application

Among with the analog data, the binary data can also be exchanged with the line
differential protection relays. The usage of the binary data is application specific and can
vary in each separate case. The demands for the speed of the binary signals vary depending
on the usage of the data. When the binary data is used as blocking signals for the line
differential protection, the transfer response is extremely high. Binary signal interchange
can be used in applications such as:
Remote position indications
Inter-tripping of the circuit breakers on both line ends
Blocking of the line differential protection during transformer inrush or current
circuit supervision failure
Protection schemes; blocking or permissive
Remote alarming.
The figure shows the overall chain to transfer binary data in an example application. The
position indication of the local circuit breaker is connected to the protection relay's input
interface and is then available for the protection relay configuration. The circuit breaker
position indication is connected to the first input of BST which is used to send information
to the remote end via communication. In the remote end, this information is handled as a
remote circuit breaker open position and it is available from the first output of BST. This
way the information can be exchanged.
IED configuration
BSTGGIO
RECV_SIG_1
SEND_SIG_1
RECV_SIG_2
SEND_SIG_2
SEND_SIG_3
RECV_SIG_3
SEND_SIG_4
RECV_SIG_4
SEND_SIG_5
RECV_SIG_5
SEND_SIG_6
RECV_SIG_6
SEND_SIG_7
RECV_SIG_7
SEND_SIG_8
RECV_SIG_8
SEND_SIG_A
RECV_SIG_A
Local CB open
position indication
RED 615
Local CB
GUID-85FE5892-DDA5-4ED9-9412-A3A48E364EFC V2 EN
Figure 406:
Example of usage of binary signal transfer for position indication change
Protection related functions
IED configuration
Remote CB open
Position indication to
SEND_SIG_1
be used e.g. for
SEND_SIG_2
blocking
SEND_SIG_3
SEND_SIG_4
SEND_SIG_5
SEND_SIG_6
SEND_SIG_7
SEND_SIG_8
Local CB open
position indication
COMMUNICATION MEDIA
Section 5
Remote CB open
BSTGGIO
Position indication to
RECV_SIG_1
be used e.g. for
RECV_SIG_2
blocking
RECV_SIG_3
RECV_SIG_4
RECV_SIG_5
RECV_SIG_6
RECV_SIG_7
RECV_SIG_8
SEND_SIG_A
RECV_SIG_A
RED 615
Local CB
797