Section 4
Protection functions
604
Level
I
2
detector
BLOCK
GUID-F890E844-B9C9-4E99-A51F-6EAB19B5239B-ANSI V2 EN
Figure 306:
Functional module diagram
Level detector
The calculated negative-sequence current is compared to the Pickup value setting. If the
measured value exceeds the Pickup value setting, the function activates the timer module.
Timer
Once activated, the timer activates the PICKUP output. Depending on the value of the set
Operating curve type, the time characteristics are according to DT or IDMT. When the
operation timer has reached the value set by Trip delay time in the DT mode or the
maximum value defined by the inverse time curve, the TRIP output is activated.
In a drop-off situation, that is, when the value of the negative-sequence current drops
below the Pickup value setting, the reset timer is activated and the PICKUP output resets
after the time delay of Reset delay time for the DT characteristics. For IDMT, the reset
time depends on the curve type selected.
For the IDMT curves, it is possible to define minimum and maximum trip times with the
Minimum trip time and Maximum trip time settings. The Machine time Mult setting
parameter corresponds to the machine constant, equal to the I
as stated by the machine manufacturer. In case there is a mismatch between the used CT
and the protected motor's nominal current values, it is possible to fit the IDMT curves for
the protected motor using the Rated current setting.
The activation of the TRIP output activates the BLK_RESTART output. The deactivation
of the TRIP output activates the cooling timer. The timer is set to the value entered in the
Cooling time setting. The BLK_RESTART output is kept active until the cooling timer is
exceeded. If the negative-sequence current increases above the set value during this
period, the TRIP output is activated immediately.
The T_ENARESTART output indicates the duration for which the BLK_RESTART output
remains active, that is, it indicates the remaining time of the cooling timer. The value is
available in the monitored data view.
Timer
TRIP
PICKUP
BLK_RESTART
1MAC059074-MB A
2
t constant of the machine,
2
615 series ANSI
Technical Manual