ABB 615 series Technical Manual page 973

Hide thumbs Also See for 615 series:
Table of Contents

Advertisement

1MAC059074-MB A
615 series ANSI
Technical Manual
Name
Type
AU_OPEN
BOOLEAN
AU_CLOSE
BOOLEAN
ITL_BYPASS
BOOLEAN
1) Not available for monitoring
2) Always direct operation
Table 866:
52 Output signals
Name
Type
SELECTED
BOOLEAN
EXE_OP
BOOLEAN
EXE_CL
BOOLEAN
OP_REQ
BOOLEAN
CL_REQ
BOOLEAN
OPENPOS
BOOLEAN
CLOSEPOS
BOOLEAN
OKPOS
BOOLEAN
OPEN_ENAD
BOOLEAN
CLOSE_ENAD
BOOLEAN
Table 867:
29DS Output signals
Name
Type
SELECTED
BOOLEAN
EXE_OP
BOOLEAN
EXE_CL
BOOLEAN
OPENPOS
BOOLEAN
CLOSEPOS
BOOLEAN
OKPOS
BOOLEAN
OPEN_ENAD
BOOLEAN
CLOSE_ENAD
BOOLEAN
Default
Description
0=False
Executes the command for open direction
0=False
Executes the command for close direction
0=False
Discards ENA_OPEN and ENA_CLOSE interlocking
when TRUE
Description
Object selected
Executes the command for open direction
Executes the command for close direction
Open request
Close request
Signal for open position of apparatus from I/O
Signal for close position of apparatus from I/O
Apparatus position is ok
Opening is enabled based on the input status
Closing is enabled based on the input status
Description
Object selected
Executes the command for open direction
Executes the command for close direction
Apparatus open position
Apparatus closed position
Apparatus position is ok
Opening is enabled based on the input status
Closing is enabled based on the input status
Section 9
Control functions
1)2)
1)2)