1MAC059074-MB A
Parameter
Values (Range)
Curve parameter C
0.02...2.00
Curve parameter D
0.46...30.00
Curve parameter E
0.0...1.0
Table 364:
67/50N Non group settings (Advanced)
Parameter
Values (Range)
Reset delay time
0...60000
Minimum trip time
40...60000
Allow Non Dir
0=False
1=True
Measurement mode
1=RMS
2=DFT
3=Peak-to-Peak
Min trip current
0.005...1.000
Min trip voltage
0.01...1.00
Correction angle
0.0...10.0
Pol reversal
0=False
1=True
IG/I0 signal Sel
1=Measured IG
2=Calculated I0
Vg or V0
1=Measured VG
2=Calculated V0
Pol quantity
3=Zero seq. volt.
4=Neg. seq. volt.
4.2.2.12
615 series ANSI
Technical Manual
Unit
Step
1
1
1
Unit
Step
ms
1
ms
1
xIn
0.001
xUn
0.01
deg
0.1

Monitored data

Table 365:
67/51N Monitored data
Name
Type
FAULT_DIR
Enum
PICKUP_DUR
FLOAT32
DIRECTION
Enum
Table continues on next page
Default
Description
2.00
Parameter C for customer programmable
curve
29.10
Parameter D for customer programmable
curve
1.0
Parameter E for customer programmable
curve
Default
Description
20
Reset delay time
40
Minimum trip time for IDMT curves
0=False
Allows prot activation as non-dir when dir info is
invalid
2=DFT
Selects used measurement mode
0.005
Minimum trip current
0.01
Minimum trip voltage
0.0
Angle correction
0=False
Rotate polarizing quantity
1=Measured IG
Measured IG or calculated I0
1=Measured VG
Selection for used Uo signal
3=Zero seq. volt.
Reference quantity used to determine fault
direction
Values (Range)
Unit
0=unknown
1=forward
2=backward
3=both
0.00...100.00
%
0=unknown
1=forward
2=backward
3=both
Section 4
Protection functions
Description
Detected fault direction
Ratio of pickup time / trip time
Direction information
357