Section 4
Protection functions
728
Q
Tripping
Pickup value
Non tripping area
GUID-A486836C-CAF2-428C-AE42-4C6172394D17 V1 EN
Figure 363:
Operating characteristics with the Pickup Value setting, Power angle (α)
being +45 and Directional mode "Forward"
Timer
Once activated, the Timer activates the PICKUP output. The time characteristics are
according to DT. When the operation timer has reached the value of Trip delay time, the
TRIP output is activated. If a drop-off situation happens, that is, the value of power drops
below Pickup value before the trip delay is exceeded, the timer reset state is activated. If
the reset timer reaches the value set by Reset delay time, the operate timer resets and the
PICKUP output is deactivated.
The Timer calculates the pickup duration value PICKUP_DUR, which indicates the
percentage ratio of the pickup situation and the set operating time (DT). The value is
available in the Monitored data view.
Blocking logic
There are three operation modes in the blocking function. The operation modes are
controlled by the BLOCK input and the global setting Configuration/System/Blocking
mode, which selects the blocking mode. The BLOCK input can be controlled by a binary
input, a horizontal communication input or an internal signal of the protection relay's
program. The influence of the BLOCK signal activation is preselected with the global
setting Blocking mode.
The Blocking mode setting has three blocking methods. In the "Freeze timers" mode, the
operate timer is frozen to the prevailing value. In the "Block all" mode, the whole function
is blocked and the timers are reset. In the "Block TRIP output" mode, the function operates
normally but the TRIP output is not activated.
area
P
1MAC059074-MB A
615 series ANSI
Technical Manual