Technical Data; Technical Revision History; Three-Phase Thermal Overload Protection, Two Time Constants 49T.275; Identification - ABB 615 series Technical Manual

Hide thumbs Also See for 615 series:
Table of Contents

Advertisement

1MAC059074-MB A
4.1.4.9
4.1.4.10
4.1.5
4.1.5.1
615 series ANSI
Technical Manual
Name
Type
T_ENA_CLOSE
INT32
TEMP_AMB
FLOAT32
49F
Enum

Technical data

Table 274:
49F Technical data
Characteristic
Operation accuracy
1)
Trip time accuracy
1) Overload current > 1.2 × Trip level temperature

Technical revision history

Table 275:
49F Technical revision history
Technical revision
C
D
E
F
Three-phase thermal overload protection, two time constants
49T

Identification

Function description
Three-phase thermal overload
protection, two time constants
Values (Range)
Unit
0...60000
s
-99...999
°C
1=Enabled
2=blocked
3=test
4=test/blocked
5=Disabled
Value
Depending on the frequency of the measured
current: f
±2 Hz
n
Current measurement: ±1.5% of the set value or
±0.002 × I
(at currents in the range of 0.01...4.00 ×
n
I
)
n
±2.0% of the theoretical value or ±0.50 s
Change
Removed the
Sensor available setting parameter
Added the AMB_TEMP input
Internal improvement.
Internal improvement.
IEC 61850
IEC 60617
identification
identification
T2PTTR
3Ith>T/G/C
Section 4
Protection functions
Description
Estimated time to deactivate
BLK_CLOSE
The ambient temperature
used in the calculation
Status
ANSI/IEEE C37.2
device number
49T
275