1MAC059074-MB A
3.15.5.3
3.15.6
3.15.6.1
3.15.6.2
3.15.6.3
615 series ANSI
Technical Manual
Signals
Table 73:
GOOSERCV_INTL Output signals
Name
Type
POS_OP
BOOLEAN
POS_CL
BOOLEAN
POS_OK
BOOLEAN
VALID
BOOLEAN
GOOSERCV_CMV function block
Function block
GUID-4C3F3A1A-F5D1-42E1-840F-6106C58CB380 V1 EN
Figure 51:
Function block
Functionality
The GOOSERCV_CMV function is used to connect GOOSE measured value inputs to the
application. The MAG_IN (amplitude) and ANG_IN (angle) inputs are defined in the
GOOSE configuration (PCM600).
The MAG output passes the received GOOSE (amplitude) value for the application.
Default value (0) is used if VALID output indicates invalid status.
The ANG output passes the received GOOSE (angle) value for the application. Default
value (0) is used if VALID output indicates invalid status.
Signals
Table 74:
GOOSERCV_CMV Output signals
Name
Type
MAG
FLOAT32
ANG
FLOAT32
VALID
BOOLEAN
Basic functions
Description
Position open output signal
Position closed output signal
Position OK output signal
Output signal
Description
Output signal (amplitude)
Output signal (angle)
Output signal
Section 3
139