Settings - ABB 615 series Technical Manual

Hide thumbs Also See for 615 series:
Table of Contents

Advertisement

1MAC059074-MB A
4.2.1.9
Table 327:
51N,51G Group settings (Basic)
Parameter
Values (Range)
Pickup value
0.010...5.000
Pickup value mult
0.8...10.0
Time multiplier
0.05...15.00
Trip delay time
40...200000
Operating curve type
1=ANSI Ext Inv
2=ANSI Very Inv
3=ANSI Norm Inv
4=ANSI Mod Inv
5=ANSI DT
6=LT Ext Inv
7=LT Very Inv
8=LT Inv
9=IEC Norm Inv
10=IEC Very Inv
11=IEC Inv
12=IEC Ext Inv
13=IEC ST Inv
14=IEC LT Inv
15=IEC DT
17=Programmable
18=RI Type
19=RD Type
Table 328:
51N,51G Group settings (Advanced)
Parameter
Values (Range)
Type of reset curve
1=Immediate
2=Def time reset
3=Inverse reset
Table 329:
51N,51G Non group settings (Basic)
Parameter
Values (Range)
Operation
1=enable
5=disable
Curve parameter A
0.0086...120.0000
Curve parameter B
0.0000...0.7120
Curve parameter C
0.02...2.00
Curve parameter D
0.46...30.00
Curve parameter E
0.0...1.0
615 series ANSI
Technical Manual

Settings

Unit
Step
xIn
0.005
0.1
0.01
ms
10
Unit
Step
Unit
Step
1
1
1
1
1
Default
Description
0.010
Pickup value
1.0
Multiplier for scaling the pickup value
1.00
Time multiplier in IEC/ANSI IDMT curves
40
Trip delay time
15=IEC DT
Selection of time delay curve type
Default
Description
1=Immediate
Selection of reset curve type
Default
Description
1=enable
Operation Disable / Enable
28.2000
Parameter A for customer programmable
curve
0.1217
Parameter B for customer programmable
curve
2.00
Parameter C for customer programmable
curve
29.10
Parameter D for customer programmable
curve
1.0
Parameter E for customer programmable
curve
Section 4
Protection functions
321

Advertisement

Table of Contents
loading

Table of Contents