Settings - ABB 615 series Technical Manual

Hide thumbs Also See for 615 series:
Table of Contents

Advertisement

1MAC059074-MB A
4.2.5.7
Table 391:
51NHA Group settings (Basic)
Parameter
Values (Range)
Pickup value
0.05...5.00
Time multiplier
0.05...15.00
Trip delay time
100...200000
Operating curve type
1=ANSI Ext Inv
2=ANSI Very Inv
3=ANSI Norm Inv
4=ANSI Mod Inv
5=ANSI DT
6=LT Ext Inv
7=LT Very Inv
8=LT Inv
9=IEC Norm Inv
10=IEC Very Inv
11=IEC Inv
12=IEC Ext Inv
13=IEC ST Inv
14=IEC LT Inv
15=IEC DT
17=Programmable
18=RI Type
19=RD Type
Table 392:
51NHA Group settings (Advanced)
Parameter
Values (Range)
Minimum trip time
100...200000
Type of reset curve
1=Immediate
2=Def time reset
3=Inverse reset
Enable reference use
0=False
1=True
Table 393:
51NHA Non group settings (Basic)
Parameter
Values (Range)
Operation
1=enable
5=disable
Curve parameter A
0.0086...120.0000
Curve parameter B
0.0000...0.7120
Table continues on next page
615 series ANSI
Technical Manual

Settings

Unit
Step
xIn
0.01
0.01
ms
10
Unit
Step
ms
10
Unit
Step
1
1
Default
Description
0.10
Pickup value
1.00
Time multiplier in IEC/ANSI IDMT curves
600
Trip delay time
15=IEC DT
Selection of time delay curve type
Default
Description
500
Minimum trip time for IDMT curves
1=Immediate
Selection of reset curve type
0=False
Enable using current reference from other
IEDs instead of stand-alone
Default
Description
1=enable
Operation Disable / Enable
28.2000
Parameter A for customer programmable
curve
0.1217
Parameter B for customer programmable
curve
Section 4
Protection functions
407