Section 4
Protection functions
4.1.9.7
Table 312:
49M Group settings (Basic)
Parameter
Values (Range)
Overload factor
1.00...1.20
Alarm thermal value
50.0...100.0
Restart thermal Val
20.0...80.0
Negative Seq factor
0.0...10.0
Weighting factor p
20.0...100.0
Time constant normal
80...4000
Time constant start
80...4000
Time constant stop
80...60000
Env temperature mode
1=FLC Only
2=Use input
3=Set Amb Temp
Env temperature Set
-20.0...70.0
Table 313:
49M Non group settings (Basic)
Parameter
Values (Range)
Operation
1=enable
5=disable
Table 314:
49M Non group settings (Advanced)
Parameter
Values (Range)
Current reference
0.30...2.00
Initial thermal Val
0.0...100.0
312

Settings

Unit
Step
0.01
%
0.1
%
0.1
0.1
%
0.1
s
1
s
1
s
1
°C
0.1
Unit
Step
Unit
Step
xIn
0.01
%
0.1
Default
Description
1.05
Overload factor (k)
95.0
Thermal level above which function gives an
alarm
40.0
Thermal level above which function inhibits
motor restarting
0.0
Heating effect factor for negative sequence
current
50.0
Weighting factor (p)
320
Motor time constant during the normal
operation of motor
320
Motor time constant during the start of motor
500
Motor time constant during the standstill
condition of motor
1=FLC Only
Mode of measuring ambient temperature
40.0
Ambient temperature used when no external
temperature measurement available
Default
Description
1=enable
Operation Disable / Enable
Default
Description
1.00
The load current leading to Temperature raise
temperature
74.0
Initial thermal level of the motor
1MAC059074-MB A
615 series ANSI
Technical Manual