Section 4
Protection functions
Table 361:
67/50N Group settings (Basic)
Parameter
Values (Range)
Pickup value
0.10...40.00
Pickup value mult
0.8...10.0
Directional mode
1=Non-directional
2=Forward
3=Reverse
Time multiplier
0.05...15.00
Operating curve type
1=ANSI Ext Inv
3=ANSI Norm Inv
5=ANSI DT
15=IEC DT
17=Programmable
Trip delay time
40...200000
Characteristic angle
-179...180
Max forward angle
0...180
Max reverse angle
0...180
Min forward angle
0...180
Min reverse angle
0...180
Voltage pickup value
0.010...1.000
Table 362:
67/50N Group settings (Advanced)
Parameter
Values (Range)
Type of reset curve
1=Immediate
2=Def time reset
3=Inverse reset
Operation mode
1=Phase angle
2=IoSin
3=IoCos
4=Phase angle 80
5=Phase angle 88
Enable voltage limit
0=False
1=True
Table 363:
67/50N Non group settings (Basic)
Parameter
Values (Range)
Operation
1=enable
5=disable
Curve parameter A
0.0086...120.0000
Curve parameter B
0.0000...0.7120
Table continues on next page
356
Unit
Step
Default
xIn
0.01
0.10
0.1
1.0
2=Forward
0.01
1.00
15=IEC DT
ms
10
40
deg
1
-90
deg
1
80
deg
1
80
deg
1
80
deg
1
80
xUn
0.001
0.010
Unit
Step
Default
1=Immediate
1=Phase angle
1=True
Unit
Step
Default
1=enable
1
28.2000
1
0.1217
1MAC059074-MB A
Description
Pickup value
Multiplier for scaling the pickup value
Directional mode
Time multiplier in IEC/ANSI IDMT curves
Selection of time delay curve type
Trip delay time
Characteristic angle
Maximum phase angle in forward direction
Maximum phase angle in reverse direction
Minimum phase angle in forward direction
Minimum phase angle in reverse direction
Voltage pickup value
Description
Selection of reset curve type
Operation criteria
Enable voltage limit
Description
Operation Disable / Enable
Parameter A for customer programmable
curve
Parameter B for customer programmable
curve
Technical Manual