Section 4
Protection functions
520
Vector group matching and elimination of the zero-sequence component
The vector group of the power transformer is numerically matched on the high voltage and
low voltage sides by means of the Winding 1 type, Winding 2 type and Clock number
settings. Thus no interposing CTs are needed if there is only a power transformer inside
the protected zone. The matching is based on phase shifting and a numerical delta
connection in the protection relay. If the neutral of a star-connected power transformer is
grounded, any ground fault in the network is perceived by the protection relay as a
differential current. The elimination of the zero-sequence component can be selected for
that winding by setting the Zro A elimination parameter.
Table 432:
87T settings corresponding to the power transformer vector groups and zero-sequence
elimination
Vector group of the
Winding 1 type
transformer
Yy0
Y
YNy0
YN
YNyn0
YN
Yyn0
Y
Yy2
Y
YNy2
YN
YNyn2
YN
Yyn2
Y
Yy4
Y
YNy4
YN
YNyn4
YN
Yyn4
Y
Yy6
Y
YNy6
YN
YNyn6
YN
Yyn6
Y
Yy8
Y
YNy8
YN
YNyn8
YN
Yyn8
Y
Yy10
Y
YNy10
YN
YNyn10
YN
Yyn10
Y
Yd1
Y
Table continues on next page
Winding 2 type
Clock number
y
Clk Num 0
y
Clk Num 0
yn
Clk Num 0
yn
Clk Num 0
y
Clk Num 2
y
Clk Num 2
yn
Clk Num 2
yn
Clk Num 2
y
Clk Num 4
y
Clk Num 4
yn
Clk Num 4
yn
Clk Num 4
y
Clk Num 6
y
Clk Num 6
yn
Clk Num 6
yn
Clk Num 6
y
Clk Num 8
y
Clk Num 8
yn
Clk Num 8
yn
Clk Num 8
y
Clk Num 10
y
Clk Num 10
yn
Clk Num 10
yn
Clk Num 10
d
Clk Num 1
1MAC059074-MB A
Zro A Elimination
Not needed
HV side
HV & LV side
LV side
Not needed
Not needed
Not needed
Not needed
Not needed
Not needed
Not needed
Not needed
Not needed
HV side
HV & LV side
LV side
Not needed
Not needed
Not needed
Not needed
Not needed
Not needed
Not needed
Not needed
Not needed
615 series ANSI
Technical Manual