Settings; Technical Data; Time Delay Off (8 Pcs) 62Tof; Identification - ABB 615 series Technical Manual

Hide thumbs Also See for 615 series:
Table of Contents

Advertisement

Section 3
Basic functions
3.17.3.5
Table 154:
62PT Non group settings (Basic)
Parameter
Values (Range)
Pulse delay time 1
0...3600000
Pulse delay time 2
0...3600000
Pulse delay time 3
0...3600000
Pulse delay time 4
0...3600000
Pulse delay time 5
0...3600000
Pulse delay time 6
0...3600000
Pulse delay time 7
0...3600000
Pulse delay time 8
0...3600000
3.17.3.6
3.17.4
3.17.4.1
170
Table 153:
62PT Output signals
Name
Type
Q1
BOOLEAN
Q2
BOOLEAN
Q3
BOOLEAN
Q4
BOOLEAN
Q5
BOOLEAN
Q6
BOOLEAN
Q7
BOOLEAN
Q8
BOOLEAN

Settings

Unit
Step
ms
10
ms
10
ms
10
ms
10
ms
10
ms
10
ms
10
ms
10

Technical data

Table 155:
62PT Technical data
Characteristic
Operate time accuracy

Time delay off (8 pcs) 62TOF

Identification

Function description
Time delay off (8 pcs)
Description
Output 1 status
Output 2 status
Output 3 status
Output 4 status
Output 5 status
Output 6 status
Output 7 status
Output 8 status
Default
Description
0
Pulse delay time
0
Pulse delay time
0
Pulse delay time
0
Pulse delay time
0
Pulse delay time
0
Pulse delay time
0
Pulse delay time
0
Pulse delay time
Value
±1.0% of the set value or ±20 ms
IEC 61850
IEC 60617
identification
identification
TOFGAPC
TOF
1MAC059074-MB A
ANSI/IEEE C37.2
device number
62TOF
615 series ANSI
Technical Manual