Load profile record LOADPROF

Functionality

The protection relay is provided with a load profile recorder. The load profile feature
stores the historical load data captured at a periodical time interval (demand interval). Up
to 12 load quantities can be selected for recording and storing in a nonvolatile memory.
The value range for the recorded load quantities is about eight times the nominal value,
and values larger than that saturate. The recording time depends on a settable demand
interval parameter and the amount of quantities selected. The record output is in the
COMTRADE format.

Quantities

Selectable quantities are product-dependent.
Table 196:
Quantity Description
Quantity Sel x
Description
Disabled
Quantity not selected
IA
Phase A current
IB
Phase B current
IC
Phase C current
IG
Neutral/ground/residual current
IA2
Phase A current, B side
IB2
Phase B current, B side
IC2
Phase C current, B side
IG2
Neutral/ground/residual current, B side
VAB
Phase-to-phase AB voltage
VBC
Phase-to-phase BC voltage
VCA
Phase-to-phase CA voltage
VA
Phase-to-ground A voltage
VB
Phase-to-ground B voltage
VC
Phase-to-ground C voltage
VAB2
Phase-to-phase AB voltage, B side
VBC2
Phase-to-phase BC voltage, B side
Table continues on next page
Section 3
Basic functions
199