Section 4
Protection functions
Parameter
Values (Range)
Curve parameter C
0.02...2.00
Curve parameter D
0.46...30.00
Curve parameter E
0.0...1.0
Table 394:
51NHA Non group settings (Advanced)
Parameter
Values (Range)
Reset delay time
0...60000
4.2.5.8
4.2.5.9
408
Unit
Step
1
1
1
Unit
Step
ms
10

Monitored data

Table 395:
51NHA Monitored data
Name
Type
PICKUP_DUR
FLOAT32
I_HARM_RES
FLOAT32
BLKD_I_REF
BOOLEAN
51NHA
Enum

Technical data

Table 396:
51NHA Technical data
Characteristic
Operation accuracy
1)2)
Pickup time
Reset time
Reset ratio
Trip time accuracy in definite time mode
Table continues on next page
Default
Description
2.00
Parameter C for customer programmable
curve
29.10
Parameter D for customer programmable
curve
1.0
Parameter E for customer programmable
curve
Default
Description
20
Reset delay time
Values (Range)
Unit
0.00...100.00
%
0.0...30000.0
A
0=False
1=True
1=Enabled
2=blocked
3=test
4=test/blocked
5=Disabled
Value
Depending on the frequency of the measured
current: f
±2 Hz
n
±5% of the set value or ±0.004 × I
Typically 77 ms
Typically 40 ms
Typically 0.96
±1.0% of the set value or ±20 ms
1MAC059074-MB A
Description
Ratio of pickup time / trip time
Calculated harmonics current
Current comparison status
indicator
Status
n
615 series ANSI
Technical Manual