Section 3
Basic functions
Parameter
Values (Range)
Web HMI timeout
1...60
SLD symbol format
1=IEC
2=ANSI
Autoscroll delay
0...30
Setting visibility
1=Basic
2=Advanced
Table 18:
IEC 61850-8-1 MMS settings
Parameter
Values (Range)
Unit mode
1=Primary
0=Nominal
2=Primary-
Nominal
1) MMS client expects primary values from event reporting and data attribute reads
2) MMS client expects nominal values from event reporting and data attribute reads; this is the default for PCM600
3) For PCM600 use only, When Unit mode is set to "Primary", the PCM600 client can force its session to "Nominal" by selecting "Primary-Nominal"
and thus parameterizing in native form. The selection is not stored and is therefore effective only for one session. This value has no effect if
selected via the LHMI.
Table 19:
Modbus settings
Parameter
Values (Range)
Operation
1=enable
5=disable
Port
1=COM 1
2=COM 2
3=Ethernet - TCP 1
Mapping selection
1...2
Address
1...254
Link mode
1=RTU
2=ASCII
TCP port
1...65535
Parity
0=none
1=odd
2=even
Start delay
0...20
End delay
0...20
CRC order
0=Hi-Lo
1=Lo-Hi
Table continues on next page
64
Unit
Step
min
1
s
1
Unit
Step
1)
2)
3)
Unit
Step
1
1
1
1
1
Default
Description
3
Web HMI login timeout
1=IEC
Single Line Diagram symbol format
0
Autoscroll delay for Measurements view
1=Basic
Setting visibility for HMI
Default
Description
0=Nominal
IEC 61850-8-1 unit mode
Default
Description
5=disable
Enable or disable this protocol instance
3=Ethernet - TCP
Port selection for this protocol instance. Select
1
between serial and Ethernet based
communication.
1
Chooses which mapping scheme will be used
for this protocol instance.
1
Unit address
1=RTU
Selects between ASCII and RTU mode. For
TCP, this should always be RTU.
502
Defines the listening port for the Modbus TCP
server. Default = 502.
2=even
Parity for the serial connection.
4
Start delay in character times for serial
connection
4
End delay in character times for serial
connections
0=Hi-Lo
Selects between normal or swapped byte order
for checksum for serial connection. Default: Hi-
Lo.
1MAC059074-MB A
615 series ANSI
Technical Manual