ABB Relion 615 Series Manual

ABB Relion 615 Series Manual

Transformer protection and control
Hide thumbs Also See for Relion 615 Series:

Advertisement

Quick Links

®
Relion
615 series
Transformer Protection and Control
RET615 ANSI
DNP3 Point List Manual

Advertisement

Table of Contents
loading

Summary of Contents for ABB Relion 615 Series

  • Page 1 ® Relion 615 series Transformer Protection and Control RET615 ANSI DNP3 Point List Manual...
  • Page 3 Document ID: 1MAC203317-MB Issued: 01/20/2010 Revision: A Product version: 2.0 © Copyright 2010 ABB. All rights reserved...
  • Page 4 Copyright This document and parts thereof must not be reproduced or copied without written permission from ABB, and the contents thereof must not be imparted to a third party, nor used for any unauthorized purpose. The software or hardware described in this document is furnished under a license and may be used, copied, or disclosed only in accordance with the terms of such license.
  • Page 5 In case any errors are detected, the reader is kindly requested to notify the manufacturer. Other than under explicit contractual commitments, in no event shall ABB be responsible or liable for any loss or damage resulting from the use of this manual or the application of the equipment.
  • Page 6 (EMC Directive 2004/108/EC) and concerning electrical equipment for use within specified voltage limits (Low-voltage directive 2006/95/EC). This conformity is the result of tests conducted by ABB in accordance with the product standards EN 50263 and EN 60255-26 for the EMC directive, and with the product standards EN 60255-6 and EN 60255-27 for the low voltage directive.
  • Page 7: Table Of Contents

    Table of contents Table of contents Section 1 Introduction................3 This manual....................3 Intended audience..................3 Product documentation................4 Product documentation set..............4 Document revision history..............5 Related documentation................6 Symbols and conventions.................6 Safety indication symbols..............6 Manual conventions................6 Functions, codes and symbols............7 Section 2 DNP3 data mappings............11 Overview....................11 Section 3 DNP3 protocol implementation..........25 DNP3 device profile................25...
  • Page 9: Section 1 Introduction

    Section 1 1MAC203317-MB A Introduction Section 1 Introduction This manual The point list manual describes the outlook and properties of the data points specific to the IED. The manual should be used in conjunction with the corresponding communication protocol manual. Intended audience This manual addresses the communication system engineer or system integrator responsible for pre-engineering and engineering for communication setup in a...
  • Page 10: Product Documentation

    Section 1 1MAC203317-MB A Introduction Product documentation 1.3.1 Product documentation set Engineering manual Engineering manual Engineering manual Installation manual Installation manual Installation manual Commissioning manual Commissioning manual Commissioning manual Operation manual Operation manual Operation manual Service manual Service manual Service manual Application manual Application manual Application manual...
  • Page 11: Document Revision History

    Some of the manuals are not available yet. 1.3.2 Document revision history Document revision/date Product series version History A/01/20/2010 First release Download the latest documents from the ABB web site http:// www.abb.com/substationautomation. RET615 ANSI Point List Manual...
  • Page 12: Related Documentation

    Section 1 1MAC203317-MB A Introduction 1.3.3 Related documentation Name of the document Document ID DNP3 Communication Protocol Manual 1MAC052460-MB Symbols and conventions 1.4.1 Safety indication symbols The caution icon indicates important information or warning related to the concept discussed in the text. It might indicate the presence of a hazard which could result in corruption of software or damage to equipment or property.
  • Page 13: Functions, Codes And Symbols

    Section 1 1MAC203317-MB A Introduction To save the changes in non-volatile memory, select Yes and press • Parameter names are shown in italics, for example: The function can be enabled and disabled with the Operation setting. • Parameter values are indicated with quotation marks, for example: The corresponding parameter values are "Enabled"...
  • Page 14 Section 1 1MAC203317-MB A Introduction Function IEC 61850 IEC 60617 ANSI Negative sequence overvoltage protection, low- NSPTOV1 U2> 47 (2) voltage side Directional ground-fault protection, low stage, low- DEFLPDEF1 >->(1) 67/51N (2) voltage side Three-phase directional overcurrent protection, low DPHLPDOC1 3I>->(1) 67/51P (2) stage, low-voltage side...
  • Page 15 Section 1 1MAC203317-MB A Introduction Function IEC 61850 IEC 60617 ANSI Fault recorder FLTMSTA Electrically latched/self resetting trip output 1 TRPPTRC1 Trip(1) 86/94-1 Electrically latched/self resetting trip output 2 TRPPTRC2 Trip(2) 86/94-2 RET615 ANSI Point List Manual...
  • Page 17: Section 2 Dnp3 Data Mappings

    Section 2 1MAC203317-MB A DNP3 data mappings Section 2 DNP3 data mappings Overview This document describes the DNP3 data points and structures available in RET615 Ver. 2.0 ANSI. The point tables show all the available DNP3 data points in this IED. The data objects in the point tables are listed in alphabetical order based on the objects' IEC61850 names.
  • Page 18 Section 2 1MAC203317-MB A DNP3 data mappings 61850 Path Default Default Disabled Description event Index Class LD0.TRPPTRC2.Tr.general TRPPTRC2 General trip output signal LD0.TRPPTRC2.Op.general TRPPTRC2 Operate input signal LD0.SSCBR1.InSprChStr.stVal SSCBR1 CB spring charging started input LD0.SSCBR1.InSprCha.stVal SSCBR1 CB spring charged input LD0.SSCBR1.InPresAlm.stVal SSCBR1 Binary pressure input for alarm LD0.SSCBR1.InPresLO.stVal...
  • Page 19 Section 2 1MAC203317-MB A DNP3 data mappings 61850 Path Default Default Disabled Description event Index Class LD0.EFHPTOC5.Str.general EFHPTOC5 Start LD0.EFHPTOC5.Op.general EFHPTOC5 Operate LD0.DEFLPTOC1.Str.general DEFLPDEF1 Start LD0.DEFLPTOC1.Op.general DEFLPDEF1 Operate LD0.INTRPTEF1.Str.general INTRPTEF1 Start LD0.INTRPTEF1.Op.general INTRPTEF1 Operate LD0.XGGIO130.Ind1.stVal X130 (BIO) X130-Input 1 LD0.XGGIO130.Ind2.stVal X130 (BIO) X130-Input 2 LD0.XGGIO130.Ind3.stVal X130 (BIO) X130-Input 3...
  • Page 20 Section 2 1MAC203317-MB A DNP3 data mappings 61850 Path Default Default Disabled Description event Index Class LD0.XGGIO100.SPCSO2.stVal X100 (PSM) X100-Output P02 LD0.XGGIO100.SPCSO3.stVal X100 (PSM) X100-Output S01 LD0.XGGIO100.SPCSO4.stVal X100 (PSM) X100-Output S02 LD0.XGGIO100.SPCSO5.stVal X100 (PSM) X100-Output S03 LD0.XGGIO100.SPCSO6.stVal X100 (PSM) X100-Output S04 LD0.LEDGGIO1.SPCSO1.stVal Alarm LEDs LED 1 LD0.LEDGGIO1.SPCSO2.stVal...
  • Page 21 Section 2 1MAC203317-MB A DNP3 data mappings 61850 Path Default Default Disabled Description event Index Class LD0.PHHPTOC1.Op.general PHHPTOC1 Operate LD0.PHHPTOC1.Op.phsA PHHPTOC1 Operate LD0.PHHPTOC1.Op.phsB PHHPTOC1 Operate LD0.PHHPTOC1.Op.phsC PHHPTOC1 Operate LD0.PHHPTOC1.InEnaMult.stVal PHHPTOC1 Enable signal for current multiplier LD0.PHHPTOC3.Str.general PHHPTOC3 Start LD0.PHHPTOC3.Str.phsA PHHPTOC3 Start LD0.PHHPTOC3.Str.phsB PHHPTOC3 Start LD0.PHHPTOC3.Str.phsC...
  • Page 22 Section 2 1MAC203317-MB A DNP3 data mappings 61850 Path Default Default Disabled Description event Index Class LD0.CCBRBRF1.InStr.stVal CCBRBRF1 CBFP start command LD0.CCBRBRF1.InPosCls.stVal CCBRBRF1 CB in closed poisition LD0.CCBRBRF1.InCBFlt.stVal CCBRBRF1 CB faulty and unable to trip LD0.DPHLPTOC1.Str.general DPHLPDOC1 Start LD0.DPHLPTOC1.Str.phsA DPHLPDOC1 Start LD0.DPHLPTOC1.Str.phsB DPHLPDOC1 Start LD0.DPHLPTOC1.Str.phsC...
  • Page 23 Section 2 1MAC203317-MB A DNP3 data mappings 61850 Path Default Default Disabled Description event Index Class LD0.PHPTUV1.Op.phsC PHPTUV1 Operate LD0.ARCSARC11.FADet.stVal ARCSARC1 Fault arc detected LD0.ARCSARC11.InRemFA.stVal ARCSARC1 Remote Fault arc detected LD0.ARCPTRC11.Op.general ARCSARC1 Operate LD0.ARCSARC21.FADet.stVal ARCSARC2 Fault arc detected LD0.ARCSARC21.InRemFA.stVal ARCSARC2 Remote Fault arc detected LD0.ARCPTRC21.Op.general ARCSARC2 Operate LD0.ARCSARC31.FADet.stVal...
  • Page 24 Section 2 1MAC203317-MB A DNP3 data mappings 61850 Path Default Default Disabled Description event Index Class CTRL.CBXCBR1.BlkCls.stVal CBXCBR1 Block closing DR.RDRE1.RcdTrg.stVal DFR Trig recording DR.RDRE1.MemClr.stVal DFR records DR.RDRE1.RcdMade.stVal DFR record made Table 3: Binary outputs 61850 Path Default Default Disable Description Index Class...
  • Page 25 Section 2 1MAC203317-MB A DNP3 data mappings 61850 Path Default Default Disable Description Index Class CTRL.CBCSWI1.Pos.Oper.ctlVal none Switch general DR.RDRE1.RcdTrg.Oper.ctlVal none Trig recording DR.RDRE1.MemClr.Oper.ctlVal none DFR records Table 4: Analog inputs 61850 Path Default Default Disabled Description Multiplier Event Index Class LD0.LPHD1.PhyHealth.stVal General state...
  • Page 26 Section 2 1MAC203317-MB A DNP3 data mappings 61850 Path Default Default Disabled Description Multiplier Event Index Class LD0.CMSTA1.AvAmps2.mag.f I_DMD_B LD0.CMSTA1.MaxAmps2.mag.f Maximum demand for Phase B LD0.CMSTA1.AvAmps3.mag.f I_DMD_C LD0.CMSTA1.MaxAmps3.mag.f Maximum demand for Phase C LD0.CMMXU2.A.phsA.instCVal.ang.f Phase currents LD0.CMMXU2.A.phsA.instCVal.mag.f Phase currents LD0.CMMXU2.A.phsA.cVal.mag.f Phase currents LD0.CMMXU2.A.phsB.instCVal.ang.f Phase currents...
  • Page 27 Section 2 1MAC203317-MB A DNP3 data mappings 61850 Path Default Default Disabled Description Multiplier Event Index Class LD0.VMMXU1.PPV.phsBC.cVal.mag.f Phase to phase voltages LD0.VMMXU1.PPV.phsCA.instCVal.ang.f Phase to phase voltages LD0.VMMXU1.PPV.phsCA.instCVal.mag.f Phase to phase voltages LD0.VMMXU1.PPV.phsCA.cVal.mag.f Phase to phase voltages LD0.CSMSQI1.SeqA.c1.instCVal.ang.f Positive Sequence Current LD0.CSMSQI1.SeqA.c1.instCVal.mag.f Positive Sequence Current LD0.CSMSQI1.SeqA.c1.cVal.mag.f...
  • Page 28 Section 2 1MAC203317-MB A DNP3 data mappings 61850 Path Default Default Disabled Description Multiplier Event Index Class LD0.FLTMSTA1.OpCnt.stVal Time LD0.FLTMSTA1.MxDifAClcA.mag.f Maximum differential current phase A LD0.FLTMSTA1.MxDifAClcB.mag.f Maximum differential current phase B LD0.FLTMSTA1.MxDifAClcC.mag.f Maximum differential current phase C LD0.FLTMSTA1.MxRstAClcA.mag.f Maximum bias current phase A LD0.FLTMSTA1.MxRstAClcB.mag.f Maximum bias current phase B LD0.FLTMSTA1.MxRstAClcC.mag.f...
  • Page 29 Section 2 1MAC203317-MB A DNP3 data mappings 61850 Path Default Default Disabled Description Multiplier Event Index Class LD0.FLTMSTA1.VoltsAB.mag.f Phase A to phase B voltage LD0.FLTMSTA1.VoltsBC.mag.f Phase B to phase C voltage LD0.FLTMSTA1.VoltsCA.mag.f Phase C to phase A voltage LD0.FLTMSTA1.VoltsN.mag.f Residual voltage LD0.FLTMSTA1.VZroSeq.mag.f Zero sequence voltage LD0.FLTMSTA1.VPsSeq.mag.f...
  • Page 30 Section 2 1MAC203317-MB A DNP3 data mappings 61850 Path Default Default Disabled Description Multiplier Event Index Class LD0.TR2PDIF1.RstA.phsC.cVal.mag.f Biasing Current CTRL.CBCSWI1.Pos.stVal CBXCBR1 Switch general DR.RDRE1.FltNum.stVal Number of recordings DR.RDRE1.MemUsed.stVal Rec. memory used RET615 ANSI Point List Manual...
  • Page 31: Section 3 Dnp3 Protocol Implementation

    The table, in combination with the Implementation table and the point list tables provides a complete configuration/interoperability guide for communicating with a device. Table 5: Device profile document DNP3 device profile document Vendor name: ABB Inc. Device name: RET615 Highest DNP level supported: Device function: For requests: Level 2+ ○...
  • Page 32 Section 3 1MAC203317-MB A DNP3 protocol implementation DNP3 device profile document ○ Always ○ When reporting event data (slave devices only) ○ When sending multi-fragment responses (slave devices only) ○ Sometimes ● Configurable as: "Only when reporting event data", or "When reporting event data or multi-fragment messages" Timeouts while waiting for: Data link ○...
  • Page 33: Dnp3 Implementation Table

    Section 3 1MAC203317-MB A DNP3 protocol implementation DNP3 device profile document ○ Only when time-tagged ○ Binary input change with time ○ Only non-time-tagged ○ Binary input change with relative time ● Configurable to send one or the other ● Configurable Sends unsolicited responses: Sends static data in unsolicited responses:...
  • Page 34 Section 3 1MAC203317-MB A DNP3 protocol implementation responded with qualifiers 00 or 01. Requests sent with qualifiers 17 or 28 will be responded with qualifiers 17 or 28. For change-event objects, qualifiers 17 or 28 are always responded. Table 6: Implementation table OBJECT REQUEST (Library will parse)
  • Page 35 Section 3 1MAC203317-MB A DNP3 protocol implementation OBJECT REQUEST (Library will parse) RESPONSE (Library will respond with) Control 3 (select) 17, 28 (index) 129 (response) echo of request relay output 4 (operate) block 5 (direct op) 6 (dir. op, noack) Analog 1 (read) 00, 01 (start-stop)
  • Page 36 Section 3 1MAC203317-MB A DNP3 protocol implementation OBJECT REQUEST (Library will parse) RESPONSE (Library will respond with) Time and 1 (read) 00, 01 (start-stop) 129 (response) 00, 01 (start-stop) 1 (default) date 06 (no range, or all) 17, 28 (index) 07 (limited qty = 1l) 08 (limited qty) 2 (write)
  • Page 37: Section 4 Glossary

    Section 4 1MAC203317-MB A Glossary Section 4 Glossary Analog input module ANSI American National Standards Institute Binary input and output Circuit breaker CBFP Circuit-breaker failure protection CROB Control relay output block Common time of occurrence. The time and date CTO object is an information object that represents the absolute time of day.
  • Page 40 Contact us ABB Inc. Distribution Automation 4300 Coral Ridge Drive Coral Springs, FL 33065, USA Phone +1 (800) 523-2620 Phone +1 954-752-6700 +1 954 345-5329 www.abb.com/substationautomation...