T_Health Function Block; Function Block; Functionality; Signals - ABB 615 series Technical Manual

Hide thumbs Also See for 615 series:
Table of Contents

Advertisement

Section 3
Basic functions
3.16.4
3.16.4.1
3.16.4.2
3.16.4.3
144

T_HEALTH function block

Function block

GUID-B5FCAE66-8026-4D5F-AC38-028E5A8171BB V1 EN
Figure 57:
Function block

Functionality

The T_HEALTH function evaluates enumerated data of "Health" data attribute. This
function block can only be used with GOOSE.
The IN input can be connected to GOOSERCV_ENUM function block, which is
receiving the LD0.LLN0.Health.stVal data attribute sent by another device.
The outputs OK, WARNING and ALARM are extracted from the enumerated input value.
Only one of the outputs can be active at a time. In case the GOOSERCV_ENUM function
block does not receive the value from the sending device or it is invalid, the default value
(0) is used and the ALARM is activated in the T_HEALTH function block.

Signals

Table 83:
T_HEALTH Input signals
Name
Type
IN1
Any
Table 84:
T_HEALTH Output signals
Name
Type
OK
BOOLEAN
WARNING
BOOLEAN
ALARM
BOOLEAN
Default
Description
0
Input signal
Description
Output signal
Output signal
Output signal
1MAC059074-MB A
615 series ANSI
Technical Manual

Advertisement

Table of Contents
loading

Table of Contents