Monitored Data - ABB 615 series Technical Manual

Hide thumbs Also See for 615 series:
Table of Contents

Advertisement

1MAC059074-MB A
4.5.9.8
4.5.9.9
615 series ANSI
Technical Manual

Monitored data

Table 584:
27R Monitored data
Name
Type
U_AMPL_A
FLOAT32
U_AMPL_B
FLOAT32
U_AMPL_C
FLOAT32
U_AMPL_AB
FLOAT32
U_AMPL_BC
FLOAT32
U_AMPL_CA
FLOAT32
27R
Enum
Technical data
Table 585:
27R Technical data
Characteristic
Operation accuracy
Pickup time
1)
Reset time
Reset ratio
Retardation time
Trip time accuracy
2)
Suppression of harmonics
1) Includes the delay of the signal output contact
2) Trip time delays do not account for variation due to pickup delay
Values (Range)
Unit
0.00...5.00
xUn
0.00...5.00
xUn
0.00...5.00
xUn
0.00...5.00
xUn
0.00...5.00
xUn
0.00...5.00
xUn
1=Enabled
2=blocked
3=test
4=test/blocked
5=Disabled
Value
±4% of setting or ±0.01 × V
±10% of setting (20 Hz > = f ≥ 10 Hz)
Minimum
30 ms
<180 ms
Depends on the relative hysteresis setting
<45 ms
±1.0% of the set value or ±20 ms
Operates only in RMS mode
Section 4
Protection functions
Description
Remanent voltage of phase A
Remanent voltage of phase B
Remanent voltage of phase C
Remanent voltage of phase to
phase AB
Remanent voltage of phase to
phase BC
Remanent voltage of phase to
phase CA
Status
(70 Hz > = f > 20 Hz)
n
Typical
Maximum
75 ms
140 ms
677