Settings - ABB 615 series Technical Manual

Hide thumbs Also See for 615 series:
Table of Contents

Advertisement

Section 6
Supervision functions
6.5.7
Table 771:
60 Non group settings (Basic)
Parameter
Values (Range)
Operation
1=enable
5=disable
Table 772:
60 Non group settings (Advanced)
Parameter
Values (Range)
Neg Seq current Lev
0.03...0.20
Neg Seq voltage Lev
0.03...0.20
Current change rate
0.01...0.50
Voltage change rate
0.25...0.90
Change rate enable
0=False
1=True
Min Op voltage delta
0.01...1.00
Min Op current delta
0.01...1.00
Seal in voltage
0.01...1.00
Enable seal in
0=False
1=True
Current dead Lin Val
0.05...1.00
872
Name
Type
V
SIGNAL
2
BLOCK
BOOLEAN
CB_CLOSED
BOOLEAN
DISCON_OPEN
BOOLEAN
MINCB_OPEN
BOOLEAN
Table 770:
60 Output signals
Name
Type
FUSEF_3PH
BOOLEAN
FUSEF_V
BOOLEAN

Settings

Unit
Step
Unit
Step
xIn
0.01
xUn
0.01
xIn
0.01
xUn
0.01
xUn
0.01
xIn
0.01
xUn
0.01
xIn
0.01
Default
Description
0
Negative phase sequence voltage
0=False
Block of function
0=False
Active when circuit breaker is closed
0=False
Active when line disconnector is open
0=False
Active when external MCB opens protected voltage
circuit
Description
Three-phase pickup of function
General pickup of function
Default
Description
1=enable
Operation Disable / Enable
Default
Description
0.03
Trip level of neg seq undercurrent element
0.10
Trip level of neg seq overvoltage element
0.15
Trip level of change in phase current
0.40
Trip level of change in phase voltage
0=False
Enabling operation of change based function
0.50
Minimum trip level of phase voltage for delta
calculation
0.10
Minimum trip level of phase current for delta
calculation
0.50
Trip level of seal-in phase voltage
0=False
Enabling seal in functionality
0.05
Trip level for open phase current detection
1MAC059074-MB A