Settings - ABB 615 series Technical Manual

Hide thumbs Also See for 615 series:
Table of Contents

Advertisement

1MAC059074-MB A
3.13.4
Table 58:
RTD input settings
Parameter
Values (Range)
Input mode
1=Not in use
2=Resistance
10=Pt100
11=Pt250
20=Ni100
21=Ni120
22=Ni250
30=Cu10
Input maximum
0...2000
Input minimum
0...2000
Value unit
1=Dimensionless
5=Ampere
23=Degrees
celsius
30=Ohm
Value maximum
-10000.0...10000.0
Value minimum
-10000.0...10000.0
Val high high limit
-10000.0...10000.0
Value high limit
-10000.0...10000.0
Value low limit
-10000.0...10000.0
Value low low limit
-10000.0...10000.0
Value deadband
100...100000
Table 59:
mA input settings
Parameter
Values (Range)
Input mode
1=Not in use
5=0..20mA
Input maximum
0...20
Input minimum
0...20
Value unit
1=Dimensionless
5=Ampere
23=Degrees
celsius
30=Ohm
Table continues on next page
615 series ANSI
Technical Manual

Settings

Unit
Step
1
1
1
1
1
1
1
1
1
Unit
Step
mA
1
mA
1
Default
Description
1=Not in use
Analogue input mode
2000
Maximum analogue input value for mA or
resistance scaling
0
Minimum analogue input value for mA or
resistance scaling
1=Dimensionless
Selected unit for output value format
10000.0
Maximum output value for scaling and
supervision
-10000.0
Minimum output value for scaling and
supervision
10000.0
Output value high alarm limit for supervision
10000.0
Output value high warning limit for supervision
-10000.0
Output value low warning limit for supervision
-10000.0
Output value low alarm limit for supervision
1000
Deadband configuration value for integral
calculation. (percentage of difference between
min and max as 0,001 % s)
Default
Description
1=Not in use
Analogue input mode
20
Maximum analogue input value for mA or
resistance scaling
0
Minimum analogue input value for mA or
resistance scaling
1=Dimensionless
Selected unit for output value format
Section 3
Basic functions
127