T_Pos_Xx Function Blocks - ABB 615 series Technical Manual

Hide thumbs Also See for 615 series:
Table of Contents

Advertisement

1MAC059074-MB A
3.17.1.9
615 series ANSI
Technical Manual

T_POS_XX function blocks

Function block
GUID-4548B304-1CCD-454F-B819-7BC9F404131F V1 EN
Figure 71:
Function blocks
Functionality
The circuit breaker position information can be communicated with the IEC 61850
GOOSE messages. The position information is a double binary data type which is fed to
the POS input.
T_POS_CL and T_POS_OP are used for extracting the circuit breaker status information.
Respectively, T_POS_OK is used to validate the intermediate or faulty breaker position.
Table 122:
Cross reference between circuit breaker position and the output of the function block
Circuit breaker position
Output of the function block
T_POS_CL
Intermediate '00'
FALSE
Close '01'
TRUE
Open '10'
FALSE
Faulty '11'
TRUE
Signals
Table 123:
T_POS_CL Input signals
Name
Type
POS
Double binary
Table 124:
T_POS_OP Input signals
Name
Type
POS
Double binary
Table 125:
T_POS_OK Input signals
Name
Type
POS
Double binary
Basic functions
T_POS_OP
T_POS_OK
FALSE
FALSE
FALSE
TRUE
TRUE
TRUE
TRUE
FALSE
Default
Description
0
Input signal
Default
Description
0
Input signal
Default
Description
0
Input signal
Section 3
159