Functionality; Signals; T_Tcmd Function Block; Function Block - ABB 615 series Technical Manual

Hide thumbs Also See for 615 series:
Table of Contents

Advertisement

Section 3
Basic functions
3.16.6.2
3.16.6.3
3.16.7
3.16.7.1
3.16.7.2
146

Functionality

The T_DIR function evaluates enumerated data of the FAULT_DIR data attribute of the
directional functions. T_DIR can only be used with GOOSE. The DIR input can be
connected to the GOOSERCV_ENUM function block, which is receiving the
LD0.<function>.Str.dirGeneral or LD0.<function>.Dir.dirGeneral data attribute sent by
another device.
In case the GOOSERCV_ENUM function block does not receive the value from the
sending device or it is invalid, the default value (0) is used in function outputs.
The outputs FWD and REV are extracted from the enumerated input value.

Signals

Table 87:
T_DIR Input signals
Name
Type
DIR
Enum
Table 88:
T_DIR Output signals
Name
Type
FWD
BOOLEAN
REV
BOOLEAN

T_TCMD function block

Function block

GUID-1CE485AE-2BCA-4D1E-92F5-417340F2589F V1 EN
Figure 60:
Function block
Functionality
The T_TCMD function is used to convert enumerated input signal to Boolean output
signals.
Default
Description
0
Input signal
Default
Description
0
Direction forward
0
Direction backward
1MAC059074-MB A
615 series ANSI
Technical Manual

Advertisement

Table of Contents
loading

Table of Contents