Monitored Data - ABB RED650 Technical Manual

Hide thumbs Also See for RED650:
Table of Contents

Advertisement

Section 3
Analog inputs
Name
CTStarPoint10
CTsec10
CTprim10
VTsec11
VTprim11
VTsec12
VTprim12
3.5
56
Values (Range)
Unit
FromObject
-
ToObject
1 - 10
A
1 - 99999
A
0.001 - 999.999
V
0.05 - 2000.00
kV
0.001 - 999.999
V
0.05 - 2000.00
kV

Monitored data

Table 13:
AISVBAS Monitored data
Name
Status
Table 14:
TRM_7I_5U Monitored data
Name
STATUS
Table 15:
TRM_9I_3U Monitored data
Name
STATUS
Table 16:
TRM_10I_2U Monitored data
Name
STATUS
Step
Default
-
ToObject
1
1
1
3000
0.001
110.000
0.05
400.00
0.001
110.000
0.05
400.00
Type
Values (Range)
INTEGER
0=Ok
1=Error
2=AngRefLow
3=Uncorrelated
Type
Values (Range)
BOOLEAN
0=Ok
1=Error
Type
Values (Range)
BOOLEAN
0=Ok
1=Error
Type
Values (Range)
BOOLEAN
0=Ok
1=Error
1MRK 505 394-UEN A
Description
ToObject= towards protected object,
FromObject= the opposite
Rated CT secondary current
Rated CT primary current
Rated VT secondary voltage
Rated VT primary voltage
Rated VT secondary voltage
Rated VT primary voltage
PID-6531-MONITOREDDATA v3
Unit
Description
-
Service value status
PID-3923-MONITOREDDATA v6
Unit
Description
-
Analogue input module
status
PID-3924-MONITOREDDATA v6
Unit
Description
-
Analogue input module
status
PID-6598-MONITOREDDATA v6
Unit
Description
-
Analogue input module
status
Line differential protection RED650 2.2 IEC
Technical manual